39
Broken Pipe Protection
When DIP switch 1-6 is enabled, the Broken Pipe Detection feature will stop the system and display Fault
14 if the drive runs at full speed without reaching the configured broken pipe pressure setpoint.
•
For example, if the feature is enabled and the pressure is set to 25 psi, and if the VFD runs at full
speed with pressure less than 25 psi for 10 minutes, the VFD will stop and fault on F14. Manual reset
is required.
•
If the system is used with a sprinkler system or is being used in another high-flow system, this pro-
tection feature should be disabled.
•
This feature can also be enabled and adjusted using the mobile app.
IMPORTANT:
The Broken Pipe Pressure setting must always be a value lower than any active Setpoint
pressure setting.
Underload Protection
The Underload Off Time determines how long the drive will wait before attempting to run following an
Underload event. The default time is Smart Reset (5 minutes, and double the time for each subsequent
reset attempt), but is user-adjustable through programming or via the mobile app from 1 minute to 48
hours.
Summary of Contents for SubDrive 15
Page 1: ...S SU UB BD DR RIIV VE E C CO ON NN NE EC CT T Owner s Manual ...
Page 14: ...14 ...
Page 22: ...22 ...
Page 30: ...30 ...
Page 36: ...36 ...
Page 40: ...40 ...
Page 56: ...56 ...
Page 62: ......
Page 63: ...ESPAÑOL ES franklinagua com SUBDRIVECONNECT Manual para propietarios ...
Page 70: ...8 ...
Page 78: ...16 ...
Page 84: ...22 ...
Page 88: ...26 ...
Page 96: ...34 ...
Page 102: ...40 ...
Page 106: ...44 ...
Page 128: ......
Page 129: ...franklinwater com FRANÇAIS FR SUBDRIVECONNECT Manuel du propriétaire ...
Page 136: ...8 ...
Page 144: ...16 ...
Page 150: ...22 ...
Page 154: ...26 ...
Page 162: ...34 ...
Page 168: ...40 ...
Page 172: ...44 ...
Page 194: ...REMARQUES ...
Page 195: ...REMARQUES ...
Page 196: ......