Installation

Overview

The mounting location of TS-RA1, TS-RA2, TS-RK units should be based on: cable run length, ease of conduit routing, 

alarm light visibility, alarm horn audible range limitations, and the distance away from hazardous areas. In addition, the 

following limitations and requirements must be met.

TANK OVERFILL ALARM

LOW Limit

(Reorder) setpoint

HIGH Limit

(Tank full) setpoint

(high)WATER

Limit setpoint

HI HI Limit

(Tank Overfill) setpoint

LO LO Limit setpoint

HAZARDOUS

AREA

TS-RK

Alarm Acknowledge

Unit

NON-HAZARDOUS

AREA

TS-RA1, or TS-RA2

Tank Overfill Alarm

(TS-RA2 shown)

FMS 

Console

NON-HAZARDOUS

AREA

Tank Filling Site

HAZARDOUS

AREA

MODEL TS-RK

SACO, MAINE 04072

INTELLIGENT CONTROLS INC.

ACKNOWLEDGE

74 INDUSTRIAL PARK ROAD

SACO, MAINE 04072

INTELLIGEN

CONTROLS

74 INDUSTRIAL

 PA

RK RD

.

TA

NK OVERFILL

 ALAR

M

MODE

TS-RA2

Figure 1: TS-RA and TS-RK Installation Overview

•   The location of the Tank Overfill Alarm and Alarm Acknowledge unit enclosures must be less than 1000 feet away from 

the 120 VAC electrical power (source) panel. 

•   The TS-RA1, or TS-RA2 Tank Overfill Alarm unit should be mounted near the fuel tank filling area.
•   The alarm light must be visible and the alarm horn must be audible at the fuel tank filling area.
•   These units should be mounted in a protected location that minimizes exposure to direct sunlight, snow and rain.
•   The TS-RK Tank Overfill Alarm Acknowledge unit should be accessible to the tank filling attendant. Access to the TS-RK 

from the filling area must be clear with no obstructions.

DO NOT install the Tank Overfill Alarm, or Alarm Acknowledge units in a volatile, combustible, or 

explosive atmosphere. Failure to do so may create an explosion hazard.
Run wiring from the Tank Sentinel console to the TS-RA1 / TS-RA2 Tank Overfill Alarm, and TS-RK 

Alarm Acknowledge units in separate conduit apart from any other wiring. All conduits must enter 

through supplied non-intrinsically safe enclosure knockouts only. Failure to do so may create an 

explosion hazard.

Warning

Warning

Summary of Contents for TS-RA1

Page 1: ...rms Installation Guide franklinfueling com 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 Fax 1 608 838 6433 Tel USA Canada 1 800 225 9787 Tel UK 44 0 1473 243300 Tel Mex 001 800 738 7610 Tel D...

Page 2: ...s associated systems When no other regulations apply follow NFPA codes 30 30A and 70 from the National Fire Protection Association Failure to follow these codes could result in severe injury death ser...

Page 3: ...Overfill Alarm and Alarm Acknowledge unit enclosures must be less than 1000 feet away from the 120 VAC electrical power source panel The TS RA1 or TS RA2 Tank Overfill Alarm unit should be mounted ne...

Page 4: ...NE 1 1 2 1 2 2 2 3 2 4 Figure 3 TS RK Mounting Details Mount the TS RA2 unit through the two 2 mounting holes provided 0 25 DIA 6 4 MM 2 HOLES 5 0 127 mm Figure 4 TS RA2 Mounting Details Wiring the Un...

Page 5: ...8 OUTPUT 1 9 OUTPUT RETURN 1 3 GROUND 1 4 1 5 REMOTE ALARM SIGNAL ACKN SWITCH LATCH MODE Console Relay Outputs NC1 C1 NO1 NC2 C2 NO2 TS RA1 TS RK 110 VAC LINE 110 VAC NEUT GND EXT ALARM CON To 110 VA...

Page 6: ...AUD L SW1 1 2 3 4 O N 2AG 3A Fuse Console Relay Outputs TS RK and TS RA2 Wiring Schematic TS RA2 SW1 Switch Position Settings factory settings are shown in bold italic Sound Ouput Level Position 1 Ton...

Page 7: ...de you select refers to the correct High High or High product threshold You can confirm the units in which the High and High High thresholds are measured under Fuel Management Systems High Product Lim...

Page 8: ...FFS 2018 000 1027 r7...

Reviews: