Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice.
Page
65
8.17
Specifications
Power supply/current consumption
(controller only)
230V~, 50Hz/40mA
Max. rated current
6 (6)A
Ambient/storage temperature
0...+40
C/-25..+50
C
Relative humidity
5 - 85%, without vapour condensation
Temperature measuring range of the NTC
10K sensor/accuracy
-
40…40
C/2
Network screw-in splice connectors
Cross section 0.5..2.5 mm
2
, tightening 0.55 Nm, isolation 7 mm
Signal screw-in splice connectors
Cross section 0.25..1.5mm
2
, tightening 0.235Nm, isolation 7 mm
Display
Colour, graphic, 480x272 with a touch panel
[Basic]
module dimensions
230x107.5 mm, height 50 mm (including 13 mm spacers)
[Basic]
module dimensions
126x66x17 mm, graphic display 128x64 pix.
[Advanced]
module dimensions
230x107.5 mm, height 50 mm (including 13 mm spacers)
[Advanced]
module dimensions
144x97x20 mm, colour graphic display 800x480 pix. with a touch
panel
Standard
PN-EN 60730-2-9, PN-EN 60730-1
Software class
A (acc. to PN-EN 60730-1)
Protection Rating
To be built into Class I instruments
Level of contamination
Level 2 (acc. to PN-EN 60730-1)
Inputs/outputs
Analogue inputs
AI0-AI6
Digital inputs
DI0-DI4
Analogue outputs
AO0-AO5, where:
- 2 outputs (0-10V)
- 2 outputs (PWM)
- 2 PWM outputs or (0-10V), programmable switching outputs
Communication outputs
3xRS485, including one separated
Outputs with a potential-free contact
- 3 (NO) normally open,
- 2 (NO/NC), switchable
Power outputs
- 2 (NO), 1000 W
- 2 (NO), 750W
Potential signalling outputs
- 3 (NO), 230 V~
8.18
Operating conditions
Controller:
•
Do not expose the controller to direct weather conditions (precipitation, sunlight) and vibrations greater than
typically during transport.
•
Do not use it in an environment with vapour condensation, and do not expose it to water.
•
The storage and transport temperatures must not exceed the range of -
25°C to 50°C.
•
It should be installed in a dry living space.
9.
Disassembly and disposal of the device
DISASSEMBLY
The disassembly of the equipment must be carried out by qualified personnel in accordance with the applicable safety
regulations. When recovering substances present in the equipment, care must be taken to avoid damage to property
and contamination of the surrounding area.
DISPOSAL
The unit must be disposed of by a specialist agency. All materials used in the unit must be disposed of or recovered in
accordance with the regulations in force. The equipment is made of the following materials:
•
Plastic materials: PA6, EPDM, Polyethylene, Rubber
•
Metal materials: galvanized steel, stainless steel, aluminium, copper (recoverable and recyclable).
•
In addition, the devices are equipped with fans with permanent magnet motors and electronic components.
At the end of their service life, these subassemblies must be dismantled with commonly available tools, such as a slot-
head screwdriver, cross-head screwdriver, flat wrench set 6-22mm.