Table 1. Program Code Quick Reference
•
Refer to Program Code Descriptions for detailed information.
•
There is a timeout feature that will return the program to normal operation in
three seconds if input is not detected at the buttons.
•
When a valid code has been entered and a programed value or option is shown
in the display, the timeout feature is disabled.
CODE FEATURE
OPTIONS
311
Flow Rate Increment
Increments by 10 at Flow Rates
Above Program Value
Increments by 1 at Flow Rates Below
Program Value
312
ID Number
0 to 99
313
Module Function
Pri, SLA, SU, ACC
315
High Flow Warning
0 to 9999
0 = Disabled
316
Low Flow Warning
0 to 9999
0 = Disabled
317
Totalizer Reset
YES = Resets to 0 at Power On
no = Stores Total Flow at Power Off
318
Flow Cutoff (Frequency)
0 to 99.9
319
Flow Cutoff (Flow Rate)
0 to 999
321
Flow Calibration (Single Point)
Calibrate One Flow Rate
322
Flow Calibration (Multiple Point)
Calibrate Two to Ten Flow Rates
E202
Invalid Code Was Entered
Re-enter Code
E204
No Flow Sensor Signal
Check Water Flow and Wiring
E206
Invalid Calibration Point
Select Different Calibration Point
E208
Memory Failure
Contact FRC