Cool-Spot in operation

User Manual

Cool-Spot.nl

9

4. Attention! Display notifications, explanation and desired actions

Displays  

Interim Defrost Cycle:
The refrigeration unit has become partially frozen, reducing the 
amount of cold air on the top. System only temporarily switches 
off the refrigeration unit. System switches on when cooler is 
defrosted. In the event of a recurring message:

Actie: 

Press the 

P button for at least 10 seconds to start the defrost 

cycle manually.
 

High pressure cooling, Temperature fault 
Reset Refrigeration unit:
This message will only appear on the display of CS refrigeration 
units that have an internal condensing unit or an external ZG 
Remote Condenser.
Due to insufficient cooling of the condensing unit or of the 
Remote Condenser, the pressure relief valve switches off the 
cooling compressor.

 

 

Low pressure cooling Temp fault auto reset: 
This message is only for CS refrigeration units with internal 
condensing unit. This fault resets automatically; if this message 
regularly appears, the CS system probably has a shortage of 
refrigerant.

Action: 

Call/email service.

C

ool

s

pot

NL

R

FRESH  TECHNOLOGY

C

ool

s

pot

NL

R

FRESH  TECHNOLOGY

CoolSpot 

®

On

Attention  !
Interim
Defrost cycle

C

ool

s

pot

NL

R

FRESH  TECHNOLOGY

CoolSpot 

®

on

Low pressure
cooling
malfuntion
auto reset

CoolSpot 

®

On

Attention  !
High pressure cooling
Temperature failure
Reset cooling unit

Causes:

Insufficient supply of cooling 
water due to insufficient water 
pressure. The water pressure 
has temporarily dropped due 
to e.g. work being carried out 
in the building. In the case of 
a remote condenser, the fan 
has failed, is defective or the 
cooler is dirty.

Action 1: 

check the water pressure/ 
water supply. For remote coo-
lers: check fan operation and/
or remove contamination from 
cooler. Check the fuse for the 
power supply to the fan

Action 2: 

Reset condensing unit pressu-
re relief valve with push button 
by firmly pressing black but-
ton manually. If this message 
recurs, call your own Technical 
Department or Cool-Spot 
service department.

Summary of Contents for Cool-Spot

Page 1: ...User Manual V3 ...

Page 2: ......

Page 3: ...l Spot controls operation and side effects 5 Side effects of Cool Spot usage in various circumstances 6 Attention Display notifications explanation and desired actions 8 FAQ Troubleshooting 11 Tips for achieving the maximum cooling effect 12 Mi light LED control 13 Washing and maintenance AIR SOCKS 15 1 2 4 3 5 6 7 8 ...

Page 4: ...layed next to On Tap 1 x for 20 vapour Tap 5 x for 100 vapour Tap once or several times The vapour drops in 5 steps Deactivating Cool Spot Tap the on off symbol The display turns dark The LED lighting switches off Off is displayed in the left corner The system will continue to ventilate for another 45 minutes Cool spot NL R FRESH TECHNOLOGY Cool spot NL R FRESH TECHNOLOGY Cool spot NL R FRESH TECH...

Page 5: ...nal the air temperature will drop from the ambient temperature to a value of around 4 5 C The temperature control of the CS system ensures that the outgoing air temperature remains between 5 and 2 degrees Celsius A temperature of 3 4 C will be displayed on the screen periodically This indicates that the cooling system is defrosting until that air temperature has been reached After a brief moment t...

Page 6: ...ust vapour to lower the risk of condensation Buffet or work surface temperature and condensation Upon activation of the Cool Spot system the buffet or work surface has the same temperature as its surroundings The vapour infused cold air from the console reduces the temperature of the surface and the area above it up to approximately 5 6 C This does not cause any condensation on the surface or the ...

Page 7: ...ve effect However this will also cause the majority of the climate to be forced across the surface which will increase the rate of energy loss and decrease the cooling effect What can you do to reduce the effect of draughts If you notice that the pattern of vapour outflow is subject to strong fluctuations is being blown away or pulled underneath the console upon activating or deactivating the exha...

Page 8: ...p transporting the condensated water to the drain has been contaminated with micro fat particles aerosols that the cooling unit has filtered from the ambient air The system deacti vates the cooling unit the surface temperature increases Action Replace or clean the condensation water pump Backup condensate pump Cool Spot has a backup condensate pump next to the main con densate pump If the main con...

Page 9: ...on units with internal condensing unit This fault resets automatically if this message regularly appears the CS system probably has a shortage of refrigerant Action Call email service Cool spot NL R FRESH TECHNOLOGY Cool spot NL R FRESH TECHNOLOGY CoolSpot On Attention Interim Defrost cycle Cool spot NL R FRESH TECHNOLOGY CoolSpot on Low pressure cooling malfuntion auto reset CoolSpot On Attention...

Page 10: ... from the supply valve Reset procedure Turn off the tap on which the stop is mounted On the drain side of the stop completely unscrew the cable gland with the blue 6 mm plastic pipe from the water stop Unscrew the water stop itself approx 1 5 turns from the tap until it is pressure free keep a cloth at hand as some drops of water will be released With a blunt object press the small red reset butto...

Page 11: ...it check whether the black button of the Iskra MS 25 16 switch is enabled 1 Vapour memory has been erased press a few times on 2 The fan is defective the display shows Fan Off call your own Technical Department check supply voltage replace fan 1 Cool Spot has been working for more than a year the nebuliser element is becoming worn and should be replaced consult your own Technical Department Option...

Page 12: ... melamine wood or other insulating material Dark coarse stone like material works better than white shiny plastic that repels cold Buffet tops made of marble granite or hard stone are better than composite Composite contains synthetic resin which has an insulating effect and is slow to absorb cooling energy Light coloured and smoothly polished buffet tops appear to have an insulating effect An imp...

Page 13: ...en this mode is on The brightness of the light can then be determined with the Brightness ring The indicator light is on when one of the functions is pressed if it is not lit and you are actually using one of the functions the batteries are probably empty Indicator light Brightness Brightness Master ON Modes programs 4x un Link Light Speed Zone on Zone out Speed Master OFF Color ring 7 Mi light LE...

Page 14: ...t on again When pairing is complete the light flashes 10 times in quick succession When the light is on long press one of the Zone Link buttons Within three seconds after the light came on Unlinking must be done with the same zone as with linking If the light does not flash 10 times quickly the disconnection is not completed please turn off the light again and follow the above steps again If the l...

Page 15: ...water at decreasing temperature For the second to last rinsing cycle a disinfectant may be added to the rinse water Allow the hose to drain centrifuge at a reduced rate or hang to dry while dripping wet Draining is recommended at low temperature max 60 C outgoing air Drying is allowed but there is a risk of shrinking In the case of persistent stains soak the air socks in detergent white wash for a...

Page 16: ...Cool Spot BV Eemnesserweg 64 1271 LW Huizen The Netherlands T 31 0 35 5244 137 www cool spot nl ...

Reviews: