210.100-IOM (JUL 2018)
Page 19
ACUAIR
®
HYGIENIC AIR UNITS
INSTALLATION
Figure 17 – Multi-Section Reconnect Sealing On AcuAir Food Grade and Sanitary Series Units
POLYURETHANE
CAULK
BASE RECONNECT FLANGE
.25 DIA
CONTINUOUS
BEAD OF CAULK
EXTERNAL RECONNECT
EXTERIOR SKIN
HCS NC GR5 .25 X .75
WITH FLANGE LOCKNUT NC .25-20
SPLIT REATTACHMENT ANGLE
Interior Finish
Caulking to be:
DOW RTV-732
Food Grade Caulk
INTERIOR WALL PANEL
POLYURETHANE FOAM
INSULATION
CONTINUOUS FINISHING BEAD
OF CAULK ALONG INNER SEAM
Figure 16 – Cross Section Of Split Wall Assembly
NOTICE
Temporary roof supports and diagonal (shipping) supports
should not be removed until the split sections are
completely reassembled.
ACUAIR FOOD GRADE OR SANITARY SERIES
ROOF RECONNECT FINISH
1. The mechanical joint between the unit sections must be
bolted and sealed with polyurethane caulking prior to applying
the roof coating.
2. Acu-Shield Roof Coating can be applied to the roof
reconnect after any exposed polyurethane caulking is dry and
when surface temperature is between 45°F and 108°F. Below
45°F, extra steps must be taken to keep the polyurethane
caulking, Acu-Shield, and metal reconnect surfaces heated
for proper application during installation. Contact Product
Service for further direction.
3. Do not apply roof coating when inclement weather is
imminent within a 24 hour period.
4. Do not apply to wet, ice, or snow covered surfaces.
5. Before applying, clean surface with wire brush or solvent
wipe (not provided).