PA3200C
15
Output charts water PA3200C
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
Supply water temperature:80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PA3210CW
max
1700
9,8
42
0,06
1,4
14,6
43
0,18
8,5
min
1050
6,2
38
0,04
0,5
10,6
48
0,13
4,8
PA3215CW
max
2700
15,6
38
0,09
2,0
24,7
45
0,30
16,8
min
1850
10,5
34
0,06
0,9
19,2
49
0,23
10,6
PA3220CW
max
3300
18,6
36
0,10
1,9
31,2
46
0,38
19,0
min
2200
12,6
34
0,07
0,9
23,7
50
0,29
11,5
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PA3210CW
max
1700
10,0
48
0,19
10,5
8,0
32
0,10
3,1
min
1050
6,1
41
0,08
2,1
5,8
34
0,07
1,8
PA3215CW
max
2700
16,0
45
0,26
13,4
13,9
33
0,17
6,3
min
1850
10,8
40
0,13
4,0
10,8
35
0,13
4,0
PA3220CW
max
3300
18,9
42
0,26
10,2
17,6
34
0,21
7,1
min
2200
12,9
39
0,15
3,6
13,4
36
0,16
4,4
Supply water temperature: 55°C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 55/35°C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PA3210CW
max
1700
9,8
48
0,35
31,3
6,3
29
0,08
2,1
min
1050
5,9
42
0,11
3,6
4,6
31
0,06
1,2
PA3215CW
max
2700
15,7
46
0,42
32,9
11,2
30
0,14
4,3
min
1850
10,8
42
0,19
8,1
8,7
32
0,11
2,8
PA3220CW
max
3300
18,7
44
0,40
22,4
14,1
31
0,17
4,9
min
2200
12,5
39
0,19
5,9
10,7
32
0,13
3,0
Supply water temperature:70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PA3210CW
max
1700
9,7
44
0,09
2,7
11,3
38
0,14
5,5
min
1050
6,1
39
0,05
0,9
8,3
41
0,10
3,2
PA3215CW
max
2700
15,6
41
0,13
3,9
19,4
39
0,24
11,1
min
1850
11,0
38
0,08
1,7
15,0
42
0,18
7,0
PA3220CW
max
3300
18,9
39
0,15
3,7
24,4
40
0,30
12,5
min
2200
12,9
36
0,09
1,6
18,6
43
0,23
7,6