PA3200C
25
EN
Overheating
The air curtain unit with electrical heating is
equipped with an overheat protection. If it is
deployed due to overheating, reset as follows:
1. Disconnect the power supply with the
isolator switch.
2. Determine the cause of overheating and
rectify the fault.
3. Remove the front hatch.
4. Press the red button located inside the
air curtain unit, at the inner gable of the
terminal box.
5. Reattach the front hatch and connect the
unit again.
All motors are equipped with an integral
thermal safety cut-out. This will operate,
stopping the air curtain should the motor
temperature rise too high. The cut-out
will automatically reset when the motor
temperature has returned to within the
motor’s operating limits.
Replacing heating elements/heating
package (E)
1. Mark and disconnect the cables to the
heating elements/package.
2. Remove the mounting screws securing the
heating elements/package in the unit and
lift the heating elements/package out.
3. Install the new heating elements/package in
reverse order to the above.
Draining the water coil (W)
The drain valve is on the underside of the coil
on the connector side. It can be accessed via
the front hatch.
Replacing the water coil (W)
1. Shut off the water supply to the unit.
2. Disconnect the connections to the water
coil.
3. Detach the plastic ends.
4. Detach the intake grille by drilling out the
rivet(s).
5. Remove the mounting screws securing the
coil in the unit and lift out.
6. Install the new coil in reverse order to the
above.
Replacing motor or impeller
1. Remove the front.
2. Remove gable end.
3. Remove the screw between motor and fan.
4. Disconnect the cables to the motor.
5. Remove the screws securing the motor and
lift it out together with the impeller.
6. Install the new motor and/or the new
impeller as above in reverse order.
Temperature control
See control pages.
Maintenance
Unit with water heating
The appliance filter should be cleaned
regularly to ensure the air curtain effect and
heat emission from the device. How often
depends on local circumstances. A clogged
filter is not a risk, but the appliance function
can fail.
1. Disconnect the power supply.
2. The front hatch is removed by removing
the screws on the top of the unit and then
detach the bent edge at the bottom. (Fig.3)
3. Remove the filter and vacuum clean or
wash it. If the filter is clogged or damaged, it
may need to be changed.
All units
Since fan motors and other components are
maintenance-free, no maintenance other than
cleaning is necessary. The level of cleaning
can vary depending on local conditions.
Undertake cleaning at least twice a year. Inlet
and exhaust grilles, impeller and elements
can be vacuum cleaned or wiped using a
damp cloth. Use a brush when vacuuming
to prevent damaging sensitive parts. Avoid
the use of strong alkaline or acidic cleaning
agents.