Assembly and operating instructions

General Instructions

Read these instructions carefully before instal-
lation and use. Keep this manual for future 
reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid if the product is used 
in the manner intended and in accordance 
with the instructions.

Application area

Panther 6-15 is a range of very quiet and ef-
ficient fan heaters for stationary use. They are 
intended for heating, drying and ventilation in 
e.g. workshops, sport halls, shops, assembly 
rooms and drying rooms. 
The mixing cabinet (accessory) allows heating 
and ventilation to be combined, through mix-
ing the return air and outdoor air.
Protection class: IP44

Function

The air is carried through the heater by a fan 
and heated by non-corrosive elements which 
are regulated by the built-in thermostat with a 
range of +5 - +35°C. The air speed is adjusta-
ble in three steps. 
 Switching on or off, selecting half or full 
output and regulating the RPM is performed 
through the control panel PP15 (ordered sepa-
rately) which is wall mounted for easy access. 

The appliance is protected from overheating 

via a built-in temperature limiter. To reset, 
see Overheating.The heater is mounted on a 
wall with a bracket, which allows direction of 
the air stream in several directions, straight 
ahead, to the left, to the right and down.

Installation

The fan heaters are intended for wall moun-
ting. The appliance must not be placed direct-
ly under a wall-outlet.

N.B.! The minimum distances given in fig. 2 
and 3 must be kept. The fan heaters must not 
be mounted on the ceiling.

 

 

Loose the bracket from the appliance by 

unscrewing the bolts. 

• Mark holes by means of the loose bracket.

Installation with mixing cabinet

Mixing cabinet PBS is available as an acces-
sory and consists of an outer wall grille and 
a walling-in frame. The walling-in frame and 
outer wall grille are built or screwed to the 
wall. The mixing cabinet and the unit are 
then fitted. See diagram 2. The hand control-
ler (PHR01, accessory) consists of a lever, a 
wall bracket, a control ball and two associated 
joints. A pull-rod is used between the joints 
(not included).

Electrical installation

The electrical installation should be carried 
out by a qualified electrician in conformity 
with prevailing regulations. The appliance 
should be preceded by an all-pole switch with 
at least 3 mm breaking gap. There are several 
ways to connect depending on the desired 
function.
On delivery the appliance is equipped with 
connections on the terminal block. With a 
connection between 
terminals 14 and 15, 
the fan RPM will be 
controlled by the regulation and the heat by 
the thermostat. Without the connection the 
thermostat will control both fan RPM and 
heat. 

When accessories are connected or when 
several

heaters are connected to each other and con-
trolled by a common accessory.

Between terminals 1 and 13, a 230V~ alarm 

signal can be obtained. When the temperature 
limiter is triggered, the voltage will drop to 
zero.
On delivery the Panther 6 – 15 fan heaters are 
for 
400V 3N~. SE135 can be connected to both 
440V3~ and 500V3~.

• Drill holes for the fixing plugs.
• Mount the bracket.
• Mount the fan heater on the bracket and 

adjust the heater to desired vertical and 
horizontal angles.

• Screw the bottom bolt in and tighten all 

bolts.

Summary of Contents for panther 6

Page 1: ...Panther 6 15 kW Original instructions 22 FR 14 IT 12 NL 10 GB 8 SE 20 DE 18 FI 16 ES 28 PL 26 RU 24 NO ...

Page 2: ...0 90 ø7 ø14 ø6 5 min 300 7 5 15 min 1800 30 min 300 min 1000 Wall Wall Ceiling Bracket B C A G D E F Mixing cabinet accessory A mm B mm C mm D mm E mm F mm G mm 660 430 365 420 445 445 420 Fig 1 Fig 2 2 Panther 6 15 ...

Page 3: ...112 31 215x185x115 PBS01 87 112 32 660x430x365 PHR01 87 112 37 PSA01 87 112 35 215x305x115 PSM01 87 112 38 180x100x70 PLR15 87 112 39 355x355x60 PFF15 87 112 44 PTRP 87 112 00 Controls and accessories PSA01 PTA01 KRT2800 RTI2 PP15 PBS01 CBT 1h 2 1 2h 4h CBT KRT1900 TTF140 Drying room kit PTRP 3 Panther 6 15 ...

Page 4: ... 3 L L L1 2 3 K1 K2 SE 06 L L L1 2 3 N 230V3 M ºC ºC K1 3 2 1 4 L L L1 2 3 X X X X X X 1 2 3 4 N 2 3 X X X 1 2 400V 3N PP15 1 1 c b a b c d 1 2 3 4 5 6 7 8 9 10111213141516 1 2 3 4 5 6 7 8 9 10 K2 L L L1 2 3 440V 3 500V 3 440V 500V 230V SE06 15 RTI2 230V 1 L 2 3 4 5 6 7 L N L N 230V t C t C Hi Lo Sensor SE 06 09 12 15 400V 3N 230V 3 4 Panther 6 15 ...

Page 5: ... 16 15 5 6 4 3 2 1 8 7 10 9 1 2 Panther SE06 15 Panther SE06 15 High speed Medium speed Low speed Panther Panther 7 10 9 8 7 6 5 4 12 11 3 2 1 14 13 16 15 10 9 8 7 6 5 4 12 11 3 2 1 14 13 16 15 Panther SE06 15 10 9 8 7 6 5 4 12 11 3 2 1 14 13 16 15 Panther SE06 15 10 9 8 7 6 5 4 12 11 3 2 1 14 13 16 15 PP15 8 PP15 Panther Panther 7 Panther SE06 15 Panther SE06 15 10 9 8 7 6 5 4 12 11 3 2 1 14 13 1...

Page 6: ...2 1 PP15 9 10 Panther Panther 4 RTI2 6 PP15 8 PP15 Panther Panther 7 Panther SE06 15 Panther SE06 15 N L 7 6 5 4 3 2 1 10 9 8 7 6 5 4 12 11 3 2 1 14 13 16 15 10 9 8 7 6 5 4 12 11 3 2 1 14 13 16 15 6 4 3 2 1 8 7 10 9 5 RTI2 3 3 Note Remove the two internal fuses 6 3A in the slave unit s Note Remove the two internal fuses 6 3A in the slave unit s 4 6 Panther 6 15 ...

Page 7: ...00V3N 13 0 520x450x510 22 SE12 87 112 52 0 6 12 900 1300 39 47 40 28 400V3N 17 3 520x450x510 22 SE15 87 112 53 0 7 5 15 900 1300 39 47 50 35 400V3N 21 7 520x450x510 22 SE135 87 112 36 0 5 10 0 7 13 5 900 1300 39 47 34 23 45 31 440V3 3 500V3 13 4 15 6 520x450x510 23 1 Conditions Distance to the unit 3 metres Directional factor 2 Equivalent absorption area 200 m2 2 t temperature rise of passing air ...

Page 8: ...2 and 3 must be kept The fan heaters must not be mounted on the ceiling Loose the bracket from the appliance by unscrewing the bolts Mark holes by means of the loose bracket Installation with mixing cabinet Mixing cabinet PBS is available as an acces sory and consists of an outer wall grille and a walling in frame The walling in frame and outer wall grille are built or screwed to the wall The mixi...

Page 9: ...tion concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance The heaters can be reconnected to 230V3 according to fig 4 The connection should be made with a cable type S05VV U A05VV R or similar For con trol H05VV5 F0 75 mm or similar may be used On the back of the appliance there are knock outs Cable...