15
NO.
Detail information
11 CN83: COMP-STATE, connect with an ac light to indicate the state of the compressor
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the light.
12 CN2: HEAT1. Pipeline Auxiliary Heater
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the pipeline auxiliary heater.
13 CN85
:
The alarm signal output of the unit (ON/OFF signal)
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the alarm signal output.
14 CN20: TP-PRO, Discharge temperature switch protection (protection code P0, prevent the compressor from over
temperature 115°C)
15 CN52: Fan relay driver port.(Only for KEM-60 DRS4)
16 CN70: EXVA, System electronic expansion valve1.
17 CN60: Outdoor units communication or HMI communication port
18 CN61: Outdoor units communication or HMI communication port
19 CN64: Fan inverter module communication ports
20 CN65: Compressor inverter module communication ports
21 CN300: Program burn in port (WizPro200RS programming device).
22 IC10: EEPROM chip
23 CN1: temperature sensors input port.
T4: outdoor ambient temperature sensor
T3A/T3B: pipe temperature sensor of the condenser
T5: water tank temperature sensor
T6A: Refrigerant inlet temperature of EVI plate heat exchanger
T6B: Refrigerant inlet temperature of EVI plate heat exchanger
24 CN16: System pressure sensor
25 CN31: Temperature sensors input port
Th: System suction temperature sensor
Taf2: Water side antifreeze temperature sensor
Two: Unit water outlet temperature sensor
Twi: Unit water inlet temperature sensor
Tw: Total water outlet temperature sensor when several units are connected in parallel
26 CN3: Module 1 temperature sensor
27 CN10: Module 2 temperature sensor
28 CN15: Detection of current of the compressor system input port
INV1
:
Detection of current of the compressor A
INV2
:
Detection of current of the compressor B
29 CN69: Temperature sensors input port
Tp1: DC inverter compressor 1 discharge temperature sensor
Tp2: DC inverter compressor 2 discharge temperature sensor
Tz/7: coil final outlet temperature sensor
Taf1: Water side antifreeze temperature
30 CN19: Low voltage protection switch. (Protection code P1)
31 CN91: Three-phase protector output switch. (Protection code E8)
32 CN58: Fan relay driver port.
33 SW3: Up button
a) Select different menus when enter menu selection.
b) For spot inspection in conditions.
SW4: Down button
a) Select different menus when enter menu selection.
b) For spot inspection in conditions.
SW5: Menu button
Press to enter menu selection, short press to return to the previous menu.
SW6: OK button
Enter the submenu or confirm the function selected by short pressing.
34 CN8: Remote function of cool/heat signal
35 CN8: Remote function of on/off signal