39
12 APPLICABLE MODELS AND MAIN PARAMETERS
Table 12-1
Model
KEM-30 DRS4
KEM-60 DRS4
Cooling capacity
kW
27.5
55
Heating capacity
kW
32.0
62
Standard cooling input
kW
10.3
21.5
Cooling rated current
A
15.9
33.1
Standard heating input
kW
10.0
20.0
Heating rated current
A
15.4
30.8
Power supply
380-415V 3N~ 50Hz
Operation control
Control of wired controller, auto startup, running state display, failure alert etc.
Safety device
High or low pressure switch, freeze-proof device, water flow volume controller,
Overcurrent device, power phase sequence device etc.
Refrigerant
Type
R-32
Water pipe system
Charging volume kg
7.9
14.0
Waterflow volume m
3
/h
5.0
9.8
Hydraulic resistance lose kPa
55
61
Water side heat exchanger
Plate heat exchanger
Max. pressure MPa
1.0
Min. pressure MPa
0.05
Inlet and outlet pipe dia.
DN40
DN50
Air side heat exchanger
Type
Fin coil model
Air flow volume m
3
/h
12500
24000
Outline dimension
N.W. of the unit
L mm
1870
2220
W mm
1000
1055
H mm
1175
1325
Net Weight
kg
300
480
Operation Weight
kg
310
490
Packing dimension
L × W × H mm
1910×1035×1370
2250×1090×1530