background image

2

GAS Dryer

CIRCUIT

 - Individual 15 amp. branch circuit fused with a 15 amp. maximum

time delay fuse or circuit breaker.

POWER SUPPLY

 - 3 wire, 120 volt single phase, 60 Hz, Alternating Current.

POWER SUPPLY CORD

 - The dryer is equipped with a 120 volt 3-wire

power cord.

Use separately fused circuits for washers and dryers, and DO NOT operate
a washer and a dryer on the same circuit.

0

60  ft.

(18.28 m)                        48 ft.(14.63 m)

1

52  ft.

(15.84 m)                        40 ft.(12.19 m)

2

44  ft.

(13.41 m)                        32 ft.  (9.75 m)

3

32  ft.

  (9.75 m)                        24 ft.  (7.31 m)

4

28  ft.

  (8.53 m)                        16 ft.   (4.87 m)

0

30  ft.

 (9.14 m)                           18 ft. (5.49 m)

1

22  ft.

 (6.71 m)                           14 ft. (4.27 m)

2

14  ft.

 (4.27 m)                           10 ft. (3.05 m)

3

          NOT RECOMMENDED

VENT HOOD TYPE

(Preferred)

MAXIMUM LENGTH

of 4” (10.2 cm) Dia. Flexible Metal Duct

Number

 of

90°

 Turns

4”

(10.2 cm)

Louvered

VENT HOOD TYPE

(Preferred)

Number

 of

90°

 Turns

MAXIMUM LENGTH

of 4” (10.2 cm) Dia. Rigid Metal Duct

(10.2 cm)

Louvered

2½"

(6.35 cm)

2½"

NEMA 10-30R

NEMA 14-30R

PRE-INSTALLATION REQUIREMENTS

Tools and Materials Required for Installation:

 1. Phillips head screwdriver.
 2. Channel-lock adjustable pliers.
 3. Carpenter's  level.
 4. Flat or straight blade screwdriver.
 5. Duct  tape.
 6. Rigid or flexible metal 4 inch (10.2 cm) duct.
 7. Vent  hood.
 8. Pipe thread sealer (Gas).
 9. Plastic  knife.

ELECTRICAL REQUIREMENTS

ELECTRIC Dryer

CIRCUIT

 - Individual 30 amp. branch circuit fused with 30 amp. minimum

time delay fuses or circuit breaker.

POWER SUPPLY

 - 3 wire or 4-wire, 240 volt, single phase, 60 Hz, Alternating

Current.

POWER SUPPLY CORD KIT

 - The dryer 

MUST

 employ a 3-conductor power

supply cord NEMA 10-30 type SRDT rated at 240 volt AC minimum, 30 amp.,
with 3 open end spade lug connectors with upturned ends or closed loop
connectors 

OR 

a 4-conductor power supply cord NEMA 14-30 type SRDT or

ST (as required) rated at 240 volt AC minimum, 30 amp., with 4 open end
spade lug connectors with upturned ends or closed loop connectors and
marked for use with clothes dryers.  If being installed in a new branch circuit
installation, manufactured (mobile) home, recreational vehicle or area which
prohibits grounding through the neutral conductor, the dryer 

MUST

 employ

a 4-conductor power supply cord NEMA 14-30 type SRDT or ST (as required)
rated at 240 volt AC minimum, 30 amp., with 4 open end spade lug connectors
with upturned ends or closed loop connectors and marked for use with
clothes dryers. See ELECTRICAL CONNECTIONS for additional instructions.

CANADA

 - A 4 wire power cord is installed on dryer.

OUTLET RECEPTACLE

 - NEMA 10-30R (3-wire) receptacle or NEMA 14-

30R (4-wire) receptacle to be located so the power supply cord is accessible
when the dryer is in the installed position.

NOTE: Do not under any
circumstances remove
grounding prong from
plug

.

GROUNDING PRONG

EXHAUST SYSTEM REQUIREMENTS

Use only 4 inch (10.2 cm) diameter (minimum) rigid or flexible 

metal 

duct and

approved vent hood which has a swing-out damper(s) that open when the
dryer is in operation. When the dryer stops, the dampers automatically close
to prevent drafts and the entrance of insects and rodents. To avoid restricting
the outlet, maintain a minimum of 12 inches (30.5 cm) clearance between
the vent hood and the ground or any other obstruction.

 The following are specific requirements for proper

and safe operation of your dryer. Failure to follow these instructions
can create excessive drying times and fire hazards.

 

Do not use plastic flexible duct to exhaust the dryer.

Excessive lint can build up inside exhaust system and create a fire hazard and
restrict air flow. Restricted air flow will increase dryer times. If your present
system is made up of plastic duct or metal foil duct, 

replace it

 with a rigid or

flexible metal duct. 

Ensure the present duct is free of any lint prior to

installing dryer duct.

 

If the dryer is not exhausted outdoors, some fine lint

will be expelled into the laundry area. 

An accumulation of lint in any area

of the home can create a health and fire hazard. 

The dryer exhaust

system MUST be exhausted to the outside of the dwelling!

 

Do not allow combustible materials (for example:

clothing, draperies/curtains, paper) to come in contact with exhaust
system. 

The dryer 

MUST NOT

 be exhausted into a chimney, a wall, a ceiling,

or any concealed space of a building which can accumulate lint, resulting in
a fire hazard.

 Exceeding the length of duct pipe or number of elbows

allowed in the "MAXIMUM LENGTH" charts 

can cause an accumulation

of lint in the exhaust system.  Plugging the system could create a fire hazard,
as well as increase drying times.

 

Do not screen the exhaust ends of the vent system,

nor use any screws or rivets to assemble the exhaust system.

 Lint can

become caught in the screen, on the screws or rivets, clogging the duct work
and creating a fire hazard as well as increasing drying times. Use an approved
vent hood to terminate the duct outdoors, and seal all joints with duct tape.
All male duct pipe fittings 

MUST

 be installed downstream with the flow of

air.

 Explosion hazard. Do not install the dryer where

gasoline or other flammables are kept or stored.

 If the dryer is installed

in a garage, it must be a minimum of 18 inches (45.7 cm) above the floor.
Failure to do so can result in death, explosion, fire or burns.

4”

(6.35 cm)

Summary of Contents for AEQ6700FS - 27" Electric Dryer

Page 1: ...TA La alimentación eléctrica para la secadora deberá cumplir con los códigos y reglamentos locales y con la última edición del Código Eléctrico Nacional ANSI NFPA 70 NOTA La alimentación de gas para la secadora deberá cumplir con los códigos y reglamentos locales y con la última edición del Código Nacional para Gases Combustibles ANSI Z223 1 NOTA La secadora está clasificada para USO DOMESTICO sol...

Page 2: ...receptacle to be located so the power supply cord is accessible when the dryer is in the installed position NOTE Do not under any circumstances remove grounding prong from plug GROUNDING PRONG EXHAUST SYSTEM REQUIREMENTS Use only 4 inch 10 2 cm diameter minimum rigid or flexible metal duct and approved vent hood which has a swing out damper s that open when the dryer is in operation When the dryer...

Page 3: ...column If the system back pressure is less than 0 75 inches of water column the system is acceptable If the manometer reading is higher than 0 75 inches of water column the system is too restrictive and the installation is unacceptable Although vertical orientation of the exhaust system is acceptable certain extenuating circumstances could affect the performance of the dryer Only the rigid metal d...

Page 4: ...1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 1234 27 68 58 5 13 97 29 75 57 13 34 29 5 12 70 2 6 03 3 8 34 86 36 35 88 90 2 25 5 72 Stacked Dryer Installation Dimensions To front of cabinet 28 25 71 76 To clear kobs 28 75 73 03 To clear door 29 5 74 93 To clear open door 53 134 62 13 5 34 29 27 68 58 Ele...

Page 5: ... MUST terminate outside the enclosure with the termination securely fastened to the mobile home structure 3 When installing a gas dryer into a mobile home a provision must be made for outside make up air This provision is to be not less than twice the area of the dryer exhaust outlet 4 This dryer MUST be fastened to the floor Mobile Home Installation Kit No 346764 is available from your dealer 5 R...

Page 6: ...door DRYER DOOR REVERSAL INSTRUCTIONS Be sure to wear gloves while reversing the door assembly 1 Open the dryer door 2 Remove the two 10 16x 50 that secures the door assembly to the front panel NOTE Remove the bottom screw first Support the door assembly firmly before removing the top screw 3 Remove the door assembly by lifting and pulling toward the center of the unit opening 4 Place door assembl...

Page 7: ... 1 The dryer MUST be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the appliance Canadian ELECTRIC Dryer DANGER Improper connection of the equipment grounding conductor can result in a risk of electrical shock Check with a licensed electrician if you are ...

Page 8: ...gs bedspreads or plastic sheets can become airtight chambers causing suffocation Place all materials in a garbage container or make materials inaccessible to children The instructions in this manual and all other literature included with this dryer are not meant to cover every possible condition and situation that may occur Good safe practice and caution MUST be applied when installing operating a...

Page 9: ...os los accesorios de tubería machos DEBEN ser instalados aguas abajo del flujo de aire NOTA No saque por ESPIGA SecadorasaGAS CIRCUITO Circuito individual derivado de 15 amp con fusibles de 15 amp de retardo máximo o disyuntor Utilice circuitos de fusibles separados para la lavadora y la secadora No opere una lavadora y una secadora en el mismo circuito ALIMENTACIÓN ELÉCTRICA Corriente alterna mon...

Page 10: ...87 1 cm 387 1 cm 387 1 cm 387 1 cm2 2 2 2 2 REQUERIMIENTOS DEL SUMINISTRO DE GAS Reemplace la tubería de conexión de cobre que no está recubrida con plástico El latón inoxidable o recubrido con plástico DEBE SER utilizado 1 La instalación DEBE hacerse cumplir con los códigos locales o en ausencia de los mismos de acuerdo con los estandares del National Fuel Gas Code Código Nacional para Gases Comb...

Page 11: ... 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 Al frente del gabinete 28 25 71 76 A las perillas claras 28 75 73 03 A las perillas puerta 29 5 74 93 En ei claro abra la puerta 53 134 62 ...

Page 12: ... adquirir con su distribuidor 5 Vealaspáginas2y3paraotrosrequísitosimportantesdeventilación 6 La instalación DEBE cumplir con las estándares aplicables de la Manufactured Home Construction Safety Standard Estándares de Seguridad y Construcción de Casas Prefabricadas Título 24 CFR Parte 32 80 del Reglamento Federal o cuando dichos estándares noseanaplicables sedebencomplirconlosestándaresdelaAmeric...

Page 13: ...puerta 1 Abre la puerta de la secadora 2 Retire los dos tornillos No 10 de 16x 50 que aseguran la puerta al panel frontal NOTA Retire primero el tornillo de abajo Sostenga firmemente la puerta antes de retirar el tornillo de arriba 3 Retire la puerta levantándola y tirando hacia el centro de la unidad 4 Coloque la puerta hacia abajo sobre una superficie plana y suave 5 Retire los dos tapones redon...

Page 14: ...e aluminio con un cordón y un enchufe de cobre o viceversa Se produce una reacción química entre el cobre y el aluminio que puede causar cortacircuitos El cableado y tomacorriente apropiado es un cordón eléctrico equipado con conductores de cobre con un tomacorriente con conductores de cobre NOTA Las secadoras que operan con un suministro de energía de 208 voltios usarán más tiempo de secado que a...

Page 15: ...cados por el fabricante podía dar lugar a daños corporales a daños materiales o a daño a la secadora Si necesita obtener piezas de recambio para su secadora póngase en contacto con el distribuidor donde compró su secadora llame 1 800 944 9044 o visitan nuestros website www frigidaire com para la Distribuidor Autorizada Company de las Piezas de Frigidaire más cercana usted Cuando se reparan los con...

Reviews: