background image

14

Overcharged System

Operate  the  unit  for  at  least  30  minutes  in  a  room

temperature of 75°F to 85°F. The top of the compressor

should be warm to the touch. This applies to a recipro-

cating compressor only. If it is cool or cold, the system

is  possibly  overcharged.  On    models  eqipped  with

Rotary compressors, check for frost or cold tempera-

tures all the way to the top of  the accumulator.
An  overcharged  system  must  be  evacuated  and

recharged. Purging off excess refrigerant is not legal or

practical, as there is no way of determining the amount

to purge.

Pressure Equalizing (System Unloading)

If an attempt is made to start the unit too soon after it has

stopped, the compressor may fail to start and will cycle

on the overload protector. This is caused by high head

pressure and low suction pressure. Allow the pressures

to  equalize  through  the  capillary  tube.  Pressure

equalizing (system unloading) will usually take 2 to 3

minutes.

Refrigerant Leaks

An undercharge of refrigerant is usually caused by a leak

in  the  system.  Such  leaks 

must 

be  located,  the

refrigerant  recovered,  and  the  leak  repaired  before

evacuating and recharging. Simply adding the refrigerant

or recharging 

will not

 permanently correct the problem

and may lead to a compressor burn out.

NOTE

: Do not replace a component because the

system is undercharged unless a nonrepairable

leak is found within the system components.

If a leak cannot be readily found, the system should be

pressurized  to  at  least  75  psig  (gauge  pressure).  If

necessary, attach a ¼” line piercing valve to the com-

pressor process tube and add enough refrigerant for

testing. (Only use the refrigerant specified on the serial

nameplate.)

3. Apply thin film of liquid flux recommended for silver

soldering to surfaces to be joined, and to surfaces

immediately adjacent to joint.

4. Align tubing so no stress is on joint. Do not move

tubing while solder is solidifying or leaks will result.

CAUTION:  During  application  of  heat,  use

wet cloths to prevent heat from conducting to

areas other than soldered joint. Use a sheet

of metal as a heat deflector to keep flame

away from flammable materials and painted

surfaces.

5. Use torch of adequate capacity so joint can be

quickly heated with minimum of heat travel to

other points. Use good grade of silver solder.

6. Solder connections. If tubing is properly cleaned

and fluxed, solder will flow readily. Use only enough

solder to make a good bond.

7. Allow joint to cool, then wash exterior with water

to remove flux.

SEALED SYSTEM

The dehumidifying system is similiar to that of a room air

conditioner,  except  for  size.  The  condenser  and

evaporator are both fin and tube coils of copper tubing

with aluminum fins.  Both coils are placed in the air

stream.

A capillary tube controls the refrigerant flow from the

condenser to the evaporator. The suction tube from the

evaporator  outlet  to  the  compressor  is  insulated  to

prevent sweating.

NOTE

: Check the performance of the dehumidifier

and electrical system before attempting to repair

the sealed system.

SEALED SYSTEM DIAGNOSIS
Undercharged System

Disconnect fan motor leads and start the unit. A slight,

uniform film of frost should form on the entire evaporator

within about 10 minutes. If it does not, the system is

possibly undercharged.
If  an  undercharged  system  is  found,  perform  the

following:
•

Leak test unit.

•

Recover refrigerant.

•

Repair Leak.

•

Evacuate and recharge unit with proper amount of

refigeratant.

NOTE

: Always leak test system after recharging.

NOTE

:  The  line  piercing  valve  (clamp-on  type)

should be used for test purposes only. It must be

removed from system after it has served its purpose.

Most leaks can be found with a Halide torch. However, for

very  small  leaks,  it  may  be  necessary  to  use  an

Electronic Leak Detector, or the soap bubble method to

pinpoint the leaks.

CAUTION

:  Be  sure  the  system  has  a  positive

pressure before using the soap bubble method of

leak detecting. A vacuum within the system could

draw in moisture and contaminants.

After servicing a system, always leak test the entire

system, especially new joints before final recharging.

Clean off any soldering flux, if used, from the joints before

Summary of Contents for FDD40J

Page 1: ...SERVICE MANUAL DEHUMIDIFIER MODELS 1 Speed 2 Speeds FDH25J FDD40J FDH30J FDD50J FDD60J P N 5995334660 May 2000 ...

Page 2: ... 8 To Remove Float 8 To Remove Bucket Switch 8 To Test Bucket Switch 9 Defrost Thermostat 9 To Remove Defrost Thermostat 9 To Test Defrost Thermostat 9 Motor Motor Bracket Blower Wheel 9 To Remove Blower Assembly 9 10 To Test Motor 10 To Remove Casters 10 Compressor 11 Permanent Split Capacitor PSC Compressor 11 Split Phase Compressor 11 To Test Compressor Motor 11 Possible Causes of Compressor Ov...

Page 3: ...igerant To Flush The System 15 Installing a New Compressor 15 16 To Remove Evaporator or Capillary Tube 16 To Remove Condenser 16 Filter Dryer 16 Evacuating Recharging 16 Equipment Needed 16 Installing Evacuation Recharging Equipment 17 Evacuating System 17 Charging The System 17 Final Leak Test 17 WIRING DIAGRAMS DATA SHEETS Electrical Wiring Diagrams Single Speed Fan Models with Reciprocating Co...

Page 4: ...ly Turn off the water supply 3 Never interfere with the proper operation of any safety device 4 USE ONLY REPLACEMENT PARTS CATALOGED FOR THIS APPLIANCE SUBSTITUTIONS MAY DEFEAT COMPLIANCE WITH SAFETY STANDARDS SET FOR HOME APPLIANCES 5 GROUNDING The standard color coding for safety ground wires is GREEN or GREEN with YELLOW STRIPES Ground leads are not to be used as current carrying conductors It ...

Page 5: ...s temperature Since this air contains less moisture and is warmer its relative humidity is lower This drier air is expelled through the side grille and mixes with the room air Place the Dehumidifier on a level surface with all four casters resting firmly on a solid floor Since the dehumidifier draws in air through the front grille and exhausts out the left side louvers the unit may be positioned a...

Page 6: ... o s s e r p m o c e h t n i h t i w e r u s s e r p n o i t c u s n w a r d s i r o t a r o p a v e e h t m o r f r o p a v t n a r e g i r f e R e r o f e b s g n i d n i w r o t o m e h t l o o c o t l l e h s e h t o t n i s i r o p a v e r u s s e r p h g i H d e s s e r p m o c g n i e b r e s n e d n o c e h t o t n i y l t c e r i d d e g r a h c s i d t n a r e g i r f e r e r u s s e r p...

Page 7: ... these screws 3 Remove two screws in upper holes in rear of cabinet flange See Figure 6d 4 Pull grille toward you so the two pins on each side of grille will pull free of holes in cabinet See Figure 6c and 6d 5 Pull grille down to release from top cover 6 Reverse procedure to reassemble To Remove Top Cover 1 Disconnect dehumidifier from electrical supply 2 Remove front grille 3 Remove two screws o...

Page 8: ...supply NOTE See Figure 7b for location of electrical wires 2 Disconnect one red and two white wires connected to Bucket Full Light One of the white wires is pigtailed to the red wire on one of the terminals 3 Disconnect two black wires connected to Humidistat Figure 7a2 To Remove Humidistat 1 Disconnect dehumidifier from electrical supply 2 Remove control knob from front of control assembly 3 Disc...

Page 9: ... Reverse procedure to reassemble Figure 8e To Remove Fan Speed Switch 2 speed models only The Fan Speed Switch is very difficult to remove without destroying it Do not attempt to remove the switch unless it is faulty Then it really doesn t matter if the switch is damaged during removal However do be careful not to damage the control assembly during removal The new switch will fit into place nicely...

Page 10: ...e thermo stat free from evaporator coil See Figure 9b 7 Reverse procedure to reassemble Figure 9b To Test Defrost Thermostat 1 Using Multimeter on resistance scale read resistance of thermostat between the two leads At room temperature above 60 F resistance should be zero 0 indicating the thermostat is closed 2 To see if thermostat opens when temperature drops to 37 F bury thermostat in bucket of ...

Page 11: ...s 10c and 10d 7 Pull blower wheel off of motor shaft and free from blower assembly 8 Lift off styrofoam scroll chassis 9 To remove motor from motor bracket remove two hex head nuts holding motor to bracket 10 Reverse procedure to reassemble Figure 10d Figure 10c NOTE When reassembling blower wheel to motor shaft make sure blower wheel is pressed onto shaft as far as it will go To Test Motor 1 Usin...

Page 12: ...D HOUSING WHEN THE COMPRESSOR IS ENERGIZED IF THIS HAPPENS A MIXTURE OF REFRIGERANT AND OIL WILL BE RELEASED THAT CAN BE IGNITED BY AN EXTERNAL HEAT SOURCE OPEN FLAME HEATER ETC ALSO IF THERE IS AIR IN THE SYSTEM WHEN THIS HAPPENS A SPARK AT THE COMPRESSOR SHELL COULD IGNITE THE REFRIGERANT AND OIL MIXTURE NOTE If compressor has a permanent split capacitor PSC motor running capacitor should be tes...

Page 13: ...rted grounded or has a high resistance leak Compressor Overload Protector An overload protector is attached to the compressor to detect excessive heat or a current overload If the overload is actuated it will shut off the current to the compressor and automatically reset itself after a short cool down period The compressor will attempt to start after the cool down period The overload is located un...

Page 14: ... expel a terminal from its insulated housing when the compressor is energized If this happens a mixture of refrigerant and oil will be released that could be ignited by an external heat source open flame heater etc Also if there is air in the system when this happens a sparkatthecompressorshellcouldignitetherefrigerant and oil mixture Charging Sealed Systems Overchargingarefrigerationsystemwithref...

Page 15: ...t use wetclothstopreventheatfromconductingto areas other than soldered joint Use a sheet of metal as a heat deflector to keep flame away from flammable materials and painted surfaces 5 Use torch of adequate capacity so joint can be quickly heated with minimum of heat travel to other points Use good grade of silver solder 6 Solder connections If tubing is properly cleaned and fluxed solder will flo...

Page 16: ...acent parts when using a torch on soldered joints If necessary use a metal heat shield or wrap a wet cloth around the tubing to reduce heat transfer To Use Refrigerant To Flush The System CAUTION Refrigerant used for flushing must be captured in a recovery bag Meter amount of refrigerant used for flushing with your charging cylinder DO NOT OVERFILL THE BAG 1 Removesuctionanddischargelinesoncompres...

Page 17: ...ended proceduredescribedunderEvacuatingand Recharging on pages 15 to 16 13 Reconnect compressor terminal leads 14 Reassemble unit NOTE OnmodelsequippedwithRotaryCompres sors the process tube is on the high side of the system Ifyouneedaccesstothelowpressureside of the system it is necessary to install a T in the suction line and add a process tube to it 4 Toreplacecapillarytube unsweattubefromevapo...

Page 18: ...pound gauge Run compressor for few minutes and leak test high side Whenleakisfound recapture refrigerantusing EPA approved recovery system repair and go back to step 1 Installing Evacuation and Recharging Equipment 1 Disconnect dehumidifier from electrical supply 2 Installprocesstubeadaptoronprocesstubeleaving as much tube as possible 3 Attach refrigeration service gauge manifold to system in foll...

Page 19: ...18 WIRING DIAGRAMS DATA SHEETS ELECTRICAL WIRING DIAGRAM Single Speed Fan Models With Reciprocating Compressors ...

Page 20: ...19 ELECTRICAL WIRING DIAGRAM 2 Speed Fan Models With Reciprocating Compressors ...

Page 21: ...20 ELECTRICAL WIRING DIAGRAM 2 Speed Fan Models With Rotary Compressor ...

Page 22: ... m o c e m a s e h t n o d e t n u o m s i l i o C r e s n e d n o c w o r e l g n i s r e s n e d n o C N P 2 2 0 2 E C H D 0 1 8 0 5 6 7 2 3 f o t r a P h t g n e L 8 3 0 1 D O 6 1 5 L T A M w o R 1 B T 4 1 h t o o m S 4 l l a W l t u O l n I 6 1 0 d e v o o r G 0 1 e p y T L l W n i M 8 1 1 0 C h c n I s n i F 5 1 l t a M m u l A 2 4 0 0 o T t e l n I y l f r e t t u B e n i l n o D I 5 5 2 3 5...

Page 23: ... i e H s n i F 8 8 o T t e l n I y l f r e t t u B e n i l n o D I 4 9 1 1 9 1 r e s n e d n o C N P 3 2 0 2 C H D B A L 1 0 0 1 6 3 7 2 3 f o t r a P h t g n e L 8 3 0 1 D O 6 1 5 L T A M w o R 2 B T 8 2 h t o o m S 4 l l a W l t u O l n I 6 1 0 d e v o o r G 4 2 e p y T L l W n i M 8 1 1 0 C h c n I s n i F 5 1 l t a M m u l A 2 4 0 0 o T t e l t u O y l f r e t t u B e n i l n o D I 6 0 1 2 0 1...

Page 24: ... i e H s n i F 0 1 1 t o T t e l n I y l f r e t t u B e n i l n o D I 4 9 1 1 9 1 r e s n e d n o C N P 3 2 0 2 C H D B A L 1 0 0 1 6 3 7 2 3 f o t r a P h t g n e L 8 3 0 1 D O 6 1 5 L T A M w o R 2 B T 8 2 h t o o m S 4 l l a W l t u O l n I 6 1 0 d e v o o r G 4 2 e p y T L l W n i M 8 1 1 0 C h c n I s n i F 5 1 l t a M m u l A 2 4 0 0 o T t e l t u O y l f r e t t u B e n i l n o D I 1 1 1 8...

Page 25: ...H s n i F 0 1 1 t o T t e l n I y l f r e t t u B e n i l n o D I 4 9 1 1 9 1 r e s n e d n o C N P 4 2 0 2 C H D B A L 1 0 2 3 6 3 7 2 3 f o t r a P h t g n e L 8 3 0 1 D O 6 1 5 L T A M w o R 3 B T 2 4 h t o o m S 4 l l a W l t u O l n I 6 1 0 d e v o o r G 8 3 e p y T L l W n i M 8 1 1 0 C h c n I s n i F 5 1 l t a M m u l A 2 4 0 0 o T t e l t u O y l f r e t t u B e n i l n o D I 1 1 1 8 0 1 ...

Reviews: