CAUTION
Install the compressor/condensing units with an appliance base plate using specified
bolts, grommets and connect compressor/condensing unit tubes (as specified by
manufacturer) to the corresponding line tubes of the application.
WARNING
Do not energize the compressor before connecting to the application.
CAUTION
Give special attention to the correct welding or other forms of connecting joints in the
system to avoid the possibilty of leaks.
CAUTION
Use a leak detector suitable for the respective refrigerant to guarantee the maximum
efficiency in controlling leaks.
CAUTION
Avoid damaging the compressor/condensint unit label during the assembly process.
CAUTION
Good refrigeration practice suggests system evacuation from both the low and high side,
achieving a minimum level of 0.14 mbar (100 µHg), with a non-condensable value of
less than 0.3%.
WARNING
Avoid the compressor/condensing unit starting under vaccum or without refrigerant
charge.
WARNING
Use the compressor/condensing unit only with the refrigerant indicated on
compressor/condensing unit label.
WARNING
System refrigerant charge when using HC refrigerants (R 600 a, R 290) must be limited
to 150 g max.
WARNING
Use the compressor/condensing unit only with the power supply indicated on the
compressor/condensing unti label.
WARNING
Use the compressor/condensing unit only with the electrical components specified by the
manufacturer. The electrical box of the compressor should be located in a position where
a safe distance from any plastic, foam, wire or any ither flammable material is ensured.
The electrical box should not be placed close to any water tray, close to insulation of
suction tubes or close to electrical connections or application wiring.
WARNING
For electrical connection, refer to applicable compressor/ condensing unit wiring
diagram.