DIGITAL INPUTS POLARITY

The digital input polarity depends on the 
“i

1P

” parameter.

i1P=CL:

 the input is activated by closing the 

contact.

i1P=OP:

 the input is activated by opening 

the contact

INSTALLATION AND MOUNTING
Instrument XR30C shall be mounted on 
vertical panel, in a 29x71 mm hole, and fixed 
using the special bracket supplied.
To obtain an IP65 protection grade use the 
front panel rubber gasket (mod. RG-C) as 
shown in figure.

The temperature range allowed for correct 
operation is 0÷60 °C. Avoid places subject to 
strong vibrations, corrosive gases, excessive 
dirt or humidity. The same recommenda-
tions apply to probes. Let air circulate by the 
cooling holes.

ELECTRICAL CONNECTIONS

The instrument is provided with screw 
terminal block to connect cables with a 
cross section up to 2,5 mm2. Before con-

necting cables make sure the power supply 
complies with the instrument’s requirements. 
Separate the probe cables from the power 
supply cables, from the outputs and the 
power connections. Do not exceed the 
maximum current allowed on each relay, in 
case of heavier loads use a suitable external 
relay.
PROBE CONNECTION
The probes shall be mounted with the bulb 
upwards to prevent damages due to casual 
liquid infiltration. It is recommended to place 
the thermostat probe away from air streams 
to correctly measure the average room 
temperature. Place the defrost termination 
probe among the evaporator fins in the 
coldest place, where most ice is formed, 
far from heaters or from the warmest place 
during defrost, to prevent premature defrost 
termination.

HOW TO USE THE HOT KEY

HOW TO PROGRAM A HOT KEY FROM THE
INSTRUMENT (UPLOAD)
1. Program one controller with the front  

 

    keypad.
2. When the controller is 

ON

, insert the “

Hot  

    key

” and push 

o

 key; the “

uPL

” message  

    appears followed a by flashing “

End

3. Push “

SET

” key and the End will stop flash 

    ing.
4. Turn OFF the instrument remove the “Hot  
    Key”, then turn it ON again.

NOTE:

 the “

Err

” message is displayed for 

failed programming. In this case push again   
key if you want to restart the upload again 
or remove the “

Hot key

” to abort the opera-

tion.
HOW TO PROGRAM AN INSTRUMENT USING  
A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a 

programmed “Hot Key” into the  

    5 PIN receptacle

 and then turn the Con 

 

    troller ON.
3. Automatically the parameter list of the  

 

    “

Hot Key

” is downloaded into the

    Controller memory, the “doL” message is  
    blinking followed a by flashing “

End

”.

4. After 10 seconds the instrument will restart  
    working with the new parameters.
5. Remove the “

Hot Key

”..

BRACKET

(PUSH TO RELEASE)

PANEL

Summary of Contents for GLE

Page 1: ...User Instructions Low Temperature Freezers Model GLE Livøvej 22 8800 Viborg Tlf 86 61 34 11 www frigor dk Low Temperature Freezers Model GLE User Instructions mODEL gle ...

Page 2: ...n order to avoid any injuries contact the sup plier for further information Never put naked flames or other igni tion sources inside the appliance Never touch the freezers interior or products in the freezer when the freezer is operating Use gloves or alike in order to avoid injuries frost bite Keep the key to the appliance away from the appliance and out of the reach of children 3 Connection to th...

Page 3: ...In order for the freezer to work to its maxi mum efficiency the cabinet should be de frosted when a approx 2mm thick ice layer has formed inside the cabinet The ice layer is easily removed with a plastic or wooden scraper Never use a sharp metal object which might will cause damage to the inner liner The defrosting frequency is determined mainly by two factors the usage pattern number of lid opening...

Page 4: ...safe storage of sensitive products In some situations the GLE freezer is also used for other applications like in laborato ries for different low temperature test Depending on the actual situation it might be necessary to change the controllers off set value in order to get a correspondence between the reading on the display and the actual temperature inside the cabinet The factory setting is an offs...

Page 5: ...e separated and far enough from each other without crossing or intertwining In case of applications in industrial environments the use of mains filters our mod FT1 in parallel with inductive loads could be useful GENERAL DESCRIPTION Model XR30C format 32 x 74 mm is a digital termostat with off cycle defrost designed for refrigeration applications at normal temper ature It provides two relay outputs ...

Page 6: ...taken place To see the kind of alarm the max min reached temperature and alarm duration do as follows 1 Push the Up or Down key 2 On the display the following mes sage is shown HAL for high temperature alarm LAL fot the minimum allarm followed by the Maximum mini mum temperature Then the tiM tiMe message is displayed followed by the Dura tion in h mm 3 Then the instrument displays the temperature ...

Page 7: ...eep pressed the Set n for more than 7s The Pr2 label will be displayed immediately fol lowed from the HY parameter NOW YOU ARE IN THE HIDDEN MENU 3 Select the required parameter 4 Press the SET key to display its value Now only the LED is blinking 5 Use o or n to change its value 6 Press SET to store the new value and move to the following parameter To exit Press SET o or wait 15s without pressing...

Page 8: ...elsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy LS US Ot ALU and ALL have to be checked and modified if necessary rES Resolution for C in 1 C dE 0 1 C allows decimal point display DEFROST IdF Interval between defrost cycles 0 120h Determines the time interval between the beginning of two defrost cycles MdF Maximum length for defrost...

Page 9: ...input is program mable in five different configurations by the i1F parameter DOOR SWITCH INPUT i1F dor It signals the door status and the corre sponding relay output status through the odc parameter no Fan normal any change CPr F_C Compressor OFF Since the door is opened after the delay time set through parameter did the door alarm is enabled the display shows the mes sage dA and the regulation resta...

Page 10: ... suitable external relay PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins in the coldest place where most ice is formed far from heaters or from the ...

Page 11: ... Housing self extinguishing ABS Case XR30C frontal 32x74 mm depth 60mm Mounting XR30C panel mounting in a 71x29mm panel cut out Protection IP20 Frontal protection IP65 with frontal gasket RG C optional Connections Screw terminal block 2 5 mm2 wiring Power supply according to the model 12Vac dc 10 24Vac dc 10 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3VA max Display 3 digits red LED 14 2...

Page 12: ...alarm at start up Alarm relay silencing 2nd relay configuration Second relay polarity oA1 ALr Digital input polarity Digital input configuration Digital input delay Number of activation of pressure switch Compressor status with open door Kind of probe Software release Map code Label Name Range C F 3 0 37 2 0 4 50 0 58 110 230 0 0 0 1 0 0 15 30 CL ºC ºF dE 8 20 it 30 Ab LS US 0 1 25 5ºC 1 255ºF 50º...

Page 13: ...p Probe selection N A N A Label Set Hy LS US Ot Ods AC CCt COn COF CH CF ldF Mdf dFd dAd Alc ALU ALL Ald dAo PbC Rel Ptb Dixell XR30C 115 volt Setting Celcius 45 3 50 0 0 1 3 0 60 5 CL C 120 0 Set 1 Ab 36 50 120 24 Ptc 3 84 Setting Farenheit 45 3 58 0 0 1 3 0 60 5 CL F 120 0 Set 0 Ab 33 58 120 24 Ptc 3 84 230 volt Ambient temperature Gross volume Gross volume Height on feet Height with open lid Wi...