11
User Instructions Low Temperature Freezers Model GLE
Livøvej 22 - 8800 Viborg - Tlf. 86 61 34 11 - www.frigor.dk
User Instructions Low Temperature Freezers Model UNI/LT
11
NOTE:
the message “
Err
” is displayed for
failed programming. In this case turn the
unit off and then on if you want to restart the
download again or remove the “
Hot key
” to
abort the operation.
ALARM SIGNALS
ALARM RECOVERY
Probe alarm “
P1
” starts some seconds after
the fault in the related probe; it automati-
cally stops some seconds after the probe
restarts normal operation. Check connec-
tions before replacing the probe.
Temperature alarms “
HA
” and “
LA
” auto-
matically stop as soon as the thermostat
temperature returns to normal values and
when defrost starts.
Alarms “
EA
” and “
CA
” (with i1F=bAL) re-
cover as soon as the digital input is
disabled.
Alarm “
CA
” (with i1F=PAL) recovers only by
switching off and on the instrument.
TECHNICAL DATA
Housing:
self extinguishing ABS.
Case: XR30C
frontal 32x74 mm; depth 60mm;
Mounting:
XR30C panel mounting in a
71x29mm panel cut-out
Protection:
IP20.
Frontal protection:
IP65 with frontal gasket
RG-C (optional).
Connections:
Screw terminal block ≤ 2,5
mm2 wiring.
Power supply:
according to the model:
12Vac/dc, ±10%; 24Vac/dc, ±10%;
230Vac ±10%, 50/60Hz, 110Vac ±10%,
50/60Hz
Power absorption:
3VA max
Display:
3 digits, red LED, 14,2 mm high.
Inputs:
1 NTC or PTC probe.
Digital input:
free contact
Relay outputs:
compressor:
SPST relay 8(3) A, 250Vac or
SPST relay 20(8)A; 250Vac
second relay:
SPDT relay 8(3) A, 250Vac or
Data storing:
on the non-volatile memory
(EEPROM).
Kind of action:
1B; Pollution grade: normal;
Software class:
A.
Operating temperature:
0÷60 °C.
Storage temperature:
-30÷85 °C.
Relative humidity:
20÷85% (no condensing)
Measuring and regulation range:
NTC probe:
-40÷110°C (-40÷230°F)
PTC probe:
-50÷150°C (-58÷302°F)
Resolution:
0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C):
±0,7 °C ±1
digit
CONNECTIONS
XR30C: 8A compressor
Alarm signals;
Message
EE
P1
HA
LA
Cause
Date or memory failure
Probe failure
Max. temp. alarm
Min. temp. alarm