Page 1
4
General Data - Ceiling Cassette FCU 50/60Hz
Note:
1)
Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.0°C WB
2)
Air volume is tested under entering air condition of 20.0°C DB and dry coil condition.
3)
All the units’ airflow value stated is at high speed.
4)
Sound pressure level is based on 11.5 dB(A) anechoic room background noise.
5)
Unit is equipped with water pump
Model
FKM
500A
600A
1000A
1400A
Air Flow
High
CMH
850
1003
1598
2550
CFM
500
590
940
1500
Medium
CMH
731
850
1360
2176
CFM
430
500
800
1280
Low
CMH
595
714
1156
1836
CFM
350
420
680
1080
Total Cooling
Capacity
High
W
4500
5700
8220
12900
Fan
Type
Centrifugal forward curved blades
Fan Motor
Type
Low Noise 4-Speed
Rated Power Input
at ESP: 0 Pa
W
76
90
145
225
Cooling Coil
Type
Seamless copper tube mechanically bonded to
aluminum hydrophilic Fin
Pipe Connection
mm(in)
DN20 (3/4") - Female Threaded
Water Flow Rate
l/s
0.22
0.27
0.40
0.62
Water Pressure
Drop
kPa
16.0
23.8
31.2
40.0
Net Weight
kg
26
35
38
40
Unit Dimension
Length
mm
570
835
835
Width
mm
570
835
835
Height
mm
260
250
290
Panel Dimension
Length
mm
650
950
Width
mm
650
950
Height
mm
55
55
Sound Pressure
Level
at ESP: 0 Pa
dB (A)
45
45
48
50
Condensate Drain Size
mm(in)
DN20 (3/4")