Technical data
ACT VS 3000 - 6000
EN - 33
11.15.11
Controlling the dryer from a remote workstation
DMC50 power module is provided with a digital input set up for dryer start up
(ON) - stop (STANDBY) mode from a remote workstation.
1-
Only qualified and skilled personnel are authorized to run electrically-
operated devices. Prior to undertaking maintenance measures at the device,
the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and
marked for maintenance measures. Please also ensure that the power
supply cannot be re-established during the works
2-
Wire a clean contact, free from electric potential, to terminals 17 and 18 to
DMC50 power module.
3-
Set the DrC parameter to REMOTE mode.
4-
Close the contact. The dryer will start up and the status bar will turn green
and display REMOTE ON.
5-
Open the contact. The dryer will stop and the status bar will turn blue and
display REMOTE STANDBY.
NOTE
!
The dryer cannot be started up and stopped from the touch screen display
when in REMOTE mode. However it is possible to carry out all other
operations, such as the condensation drain test, the management of
alarms/service warnings, and access functions menus.
Only a clean contact free from electric potential and suitable for low
voltage must be used. Ensure there is adequate insulation on
potentially hazardous live parts.
11.15.12
How the alarm / service warning flagging contact operates
DMC50 power module is provided with a clean contact, free from electric potential, for remotely flagging dryer
alarm/warning conditions.
1-
Set the ACM (Alarm Contact Management) parameter to the required mode (see section
10.15.14
).
Dryer powered and absence of the conditions checked with the ACM parameter settings
Dryer not powered or presence of at least one of the conditions checked with the ACM parameter
settings
11.15.13
How the RS485 serial communication port operates
DMC50 power module is provided with a data communication connection for remote dryer monitoring operations.
Contact the manufacturer for further information on using this application.
If the fieldbus is used, is mandatory to install a galvanic isolator between the DMC50 and the communication network, in
order to guarantee the DMC50 safety.
2-