37
7425MUM661
Model: CWB FC
- Use and Maintenance Manual
Rev02
Cause
Alarm signal or
symptom
Solution
Execution
4. Intervention of the water differential pressure switch
Taps of the machine are turned off
A03
Evap. Flow switch alarm
Open the valves
User
Water circulation pump blocked or
defective
A03
Evap. Flow switch alarm
Unlock or replace the pump
Specialised
personnel
Water pump stopped
A03
Evap. Flow switch alarm
Pump icon lit.
Check the voltage at the coil
of the contactors of the pump
and the continuity of the coil
itself
Specialised
personnel
5. Intervention of the low-pressure pressure transducer
Refrigerant filter clogged or
thermostatic valve stuck
Pipe downstream from
the component covered
with frost.
Check and replace
Specialised
personnel
Insufficient refrigerant charge
See point 8
6. Fans don't start
Very low outside air temperatures and
consequent intervention of the
condensation control
Fan icon off.
Condensation pressure
normal
The machine is working
anyway
No voltage output from the fan-speed
regulator
Fan icon on and fans
stopped
Check the voltage output from
the regulator and replace, if
necessary
Specialised
personnel
Intervention of the circuit breaker
protection inside the fan
A51
Circuit 1 fans overload
Check that the working
conditions of the machine
(outside air temperature) are
compatible with the operating
limits. Wait for the fan motor
to cool.
User
Fan fuse blown.
Fan icon on and fans
stopped
Look for short circuits in the
motor windings of the fans.
Check the fan roller bearings.
Specialised
personnel
Electrical connections of the fans
loose
Fan icon on and fans
stopped
Check and tighten
Specialised
personnel
Intervention of fans 1,2 or 3 internal
thermal protection
AF1
Circuit 1 fans overload
Check that the working
conditions of the machine
(outside air temperature) are
compatible with the operating
limits.
Wait for the fan motor to cool.
User