19
7425MUM651
Model: QBS
- Use and Maintenance Manual
Rev. 02
6.10
T
ABLE OF STANDARD PARAMETERS CONFIGURATION
Below there is a table of most important parameters and their factory setting. To modify the parameter
contact our company.
Parameter Function
Factory setting
SP
Working setpoint
0°C//32°F
r0
Working setpoint differential
5K
r1
Minimum working setpoint
0°C//32°F
r2
Maximum working setpoint
25°C//77°F
r6
Type of working setpoint:
•
Absolute setpoint r6=0
•
Relative setpoint r6=1: temp. read by probe 1 – working setpoint
1
r7
Forced off of compressors
4°C//39,2°F
r8
Differential of parameter r7
[At r7+r8 value the compressor could be switched on]
2K
A1
Temperature the alarm of low temperature is activated AL1
4°C//39,2°F
A4
Temperature the alarm of high temperature is activated AL2
50°C//122°F
A10
Differential of parameter A1
[At A1+A10 value the alarm AL1 will be deactiveted]
2K
A11
Differential of parameter A4
[At A4-A11 value the alarm AL2 will be deactiveted]
5K
6.11
A
LTERNATIVE METHOD OF TEMPERATURE REGULATION
The electronic controller allows to regulate the outlet working temperature with an absolute logic in
function of the temperature read by probe 1.
In that way, the SP value is the absolute regulation setpoint like in the following image.
To set this kind of working mode, please set the following values in that way (see paraghaph
5.9
Setting configuration parameters
).
Parameter Function
Suggested value
r1
Minimum working setpoint
6°C//42,8°F
r6
Type of working setpoint:
•
Absolute setpoint r6=0
•
Relative setpoint r6=1: temp. read by probe 1 – working setpoint
0