2.5 Connection options with standard delivery
2.5.1 System 0 (DHW tank / one heating circuit)
This system is preset in the delivery configuration. If the components are connected as shown in the following
diagram, no further parameterisation is required.
M
N
AUF
ZU
N
AUF
ZU
L
N
L1
N
L
N
Mischer 2
(30)
HKP 0 /
Brennerrelais
(34)
Heizkreis-
pumpe 1
(33)
Heizkreis-
pumpe 2
(32)
Mischer 1
(31)
PWM/0-10V
Pumpe 1 (26)
V
orlauf-
fühler 1 (23)
V
orlauf-
fühler 2 ( 22)
Durchfluss-
messer (12)
L
N
Netz
(29)
L
N
Pumpe 1
(28)
L
V
Fühler 1 (18)
Fühler 2 (17)
Betriebs-
signal
(35)
2
2
2
3
3
4
3
M
Fröling PECO
DHW tank
Unicell NT-S / BWP
Flow temperature sensor 1
Heating circuit pump 1
Mot. mixing valve 1
Cold water
Domestic hot water
Pump 1
HKP0
Sensor 1
Balancing
valve
Note:
The minimum flow through rate of the Pellet boiler shall be respected!
(e.g. with zone valve)
PECO 15 = 260 l/h
PECO 30 = 520 l/h
PECO 20 = 340 l/h
PECO 32 = 550 l/h
PECO 25 = 430 l/h
PECO 35 = 600 l/h
If a zone valve is used for the minimum flow volume:
❒ In the service menu of the boiler, set the “
Pump output for skimming
” parameter to “HCP 0”
Power connection and wiring
2
Connection options with standard delivery
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
29