4.1.6 Heating - General settings
System menu
Heating
General settings
service
Correction value for external sensor
If the outside temperature sensor shows an incorrect
value, the value can be adjusted using this parameter.
Heating circuit module to which the external sensor is
connected (0 = core module)
If the outside temperature sensor is not connected to the
core module, the address of the relevant heating circuit
1 must be set here (sensor 1 on relevant
module).
Using room sensor inputs for room thermostat
NOTICE! This parameter influences all sensor connections
to which an analogue room temperature sensor can be
connected!
▪ NO: At the sensor connector of the room sensor, a
room sensor must be connected to control the room
temperature.
▪ YES: At the sensor connector of the room sensor, room
thermostats can be connected to control the room
temperature.
– Contact of room thermostat open: Heating circuit pump
deactivated, mixing valve is closed
– Contact of room thermostat closed: Heating circuit pump
and mixer control active
4
Parameters overview
Heating
42
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com