4.4.2 Buffer tank - Temperatures
System menu
Buffer tank
Heating circuit release from following buffer tank
temperature
Temperature value which must be reached to release the
heating circuit pumps in the top part of the buffer tank.
NOTICE! This parameter applies for all available heating
circuits!
Buffer tank fully loaded if temperature difference between
boiler and bottom buffer tank
From this difference between the boiler temperature
setpoint that has been set and the current temperature in
the lower part of the buffer tank, buffer tank loading is
stopped.
Storage tank – storage tank difference
Prerequisite: Variant 3
Difference, which must be given for loading a storage tank
e.g. in an adjacent building. If this difference is not
reached, the storage tank loading stops.
4.4.3 Buffer tank - Service
System menu
Buffer tank
Enable heating circuit pump 0 according to top buffer
temp.
▪ NO: Release of heating circuit pump 0 according to the
boiler temperature parameter “
Minimum boiler
temperature to release all pumps
”
▪ YES: Release of heating circuit pump 0 according to the
temperature in the top part of the buffer tank parameter
“Heating circuit release from following
buffer tank temperature”
Sensor input of storage tank top sensor
Sensor input to which the sensor in the top part of the
buffer tank is connected.
Sensor input of storage tank sensor 2-7
The number of sensors displayed depends on the
configuration. All of the configured sensors are used to
calculate the storage tank charge status.
Sensor input of storage tank middle sensor
Sensor input to which the sensor in the mid area of the
buffer tank is connected.
Sensor input of storage tank bottom sensor
Sensor input to which the sensor in the bottom part of the
buffer tank is connected.
Pump output of storage tank pump
Pump outlet to which the buffer loading pump is
connected.
Control of storage tank pump
Definition of control signal for pump type used.
⇨ See "Activation options of pump outlets" [page 74]
Minimum storage tank pump speed
Adjustment of the minimum speed to the pump type (set
mode of pump in accordance with pump manufacturer).
Maximum buffer tank pump speed
If you need to limit the maximum speed of the store
loading pump for systemic reasons, you can do so by
adjusting this parameter.
4
Parameters overview
Buffer tank
52
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Summary of Contents for Lambdatronic P 3200
Page 85: ...6 Notes Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 85...
Page 86: ...6 Notes 86 Froling GesmbH A 4710 Grieskirchen Industriestra e 12 www froeling com...
Page 87: ...Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 87...