Delivered amount of pellets at 100% feed
Values have already been predefined based on the boiler
type and boiler rating. If the required amount of pellets was
recalculated, this setting can be used to adjust the pellet
amount for calculating pellet consumption.
4.7 Network pump
4.7.1 Network pump - Status
System menu
Network pump
Network return temperature
Display of the current return temperature of the remote
line.
Network pump speed
Specifies the current speed of the network pump.
Return temperature distributor 1
Prerequisite: Variant 1 and feeder pump for distributor 1
installed
Display of the current return temperature from distributor 1.
Speed, distributor 1 pump
Prerequisite: Variant 1 and pump for distributor 1 installed
Display of the current speed of distributor 1 pump.
Return temperature distributor 2 … 4
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
Display of the current return temperature from distributor
2 ...4.
Speed, distributor 2 ...4 pump
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
Display of the current speed of the distributor 2 … 4 pump.
4.7.2 Network pump - Temperatures
System menu
Network pump
Network return setpoint
Prerequisite: Network pump installed
The network return setpoint is regulated to the value set
here. When the network return temperature reaches the
specified value, the network pumps starts up at minimum
speed.
Return temperature setpoint distributor 1
Prerequisite: Variant 1 and pump for distributor 1 installed
The return temperature from distributor 1 is regulated to
the value set here. When the return temperature from
distributor 1 reaches the specified value, the pump for
distributor 1 starts up at minimum speed.
Parameters overview
4
Network pump
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
57
Summary of Contents for Lambdatronic P 3200
Page 85: ...6 Notes Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 85...
Page 86: ...6 Notes 86 Froling GesmbH A 4710 Grieskirchen Industriestra e 12 www froeling com...
Page 87: ...Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 87...