Activation of distributor 2 ... 4 pump
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
Definition of control signal for pump type used.
⇨ See "Activation options of pump outlets" [page 74]
Minimum speed for distributor 2 ... 4 pump
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
Adjustment of the minimum speed to the pump type (set
mode of pump in accordance with pump manufacturer).
Maximum speed for distributor 2 ... 4 pump
Prerequisite: Variant 2 or variant 3 and pump for distributor
2 ... 4 installed
If you need to limit the maximum speed of distributors 2 ...
4 pump for systemic reasons, you can do so by adjusting
this parameter.
4.8 Difference regulator
4.8.1 Difference regulator - Status
System menu
Diff. control
Heat source temperature
Display of the current heat source temperature of the
differential controller (e.g. tiled stove with water pocket,
…).
Heat sink sensor
Display of the current temperature of the heat sink for the
differential controller (e.g. layered tank, …).
Pump speed
Specifies the current speed of the differential controller
pump.
4.8.2 Difference regulator - Temperatures
System menu
Diff. control
Startup difference
Temperature difference between heat source and heat
sink which must be reached to activate the pump of the
differential controller.
Shutdown difference
If the temperature difference between the heat source and
the heat sink falls below this value, the pump of the
differential controller is deactivated.
Minimum temperature for heat source
If the temperature in the heat source falls below this value
the differential controller will be deactivated.
Maximum temperature for heat sink
When the heat sink reaches this value, the pump of the
differential controller is deactivated.
Parameters overview
4
Difference regulator
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
59