Residual oxygen content setpoint
Residual oxygen content which is regulated during
“
Heating
” status.
Residual oxygen above which the lambda probe is allowed
to switch off
If the boiler switches to “
Boiler off
” or “
Off
” mode, the
lambda probe heating remains active for at least 1 hour,
up to a maximum of 24 hours. If the residual oxygen
content exceeds the value set here, the lambda probe
heating is switched off.
Set - Lambda probe
System menu
System
Setting
Lambda probe
Residual oxygen content
Display of the current residual oxygen content.
Lambda probe status
The following status displays are possible:
▪ Off
▪ Pre-heating
▪ Normal operation
▪ Cooling
▪ Reheating
▪ Error
Lambda probe type
Setting the Lambda probe type used:
▪ Bosch broadband probe
(item number: 69001A, “broadband probe” socket)
▪ NTK broadband probe
(item number: 69003, “broadband probe” socket)
▪ Bosch switching-type sensor
(type LSM11, “Lambda probe” socket)
▪ NTK switching-type sensor
(type OZA685, item number: 69400, “Lambda probe”
socket)
Lambda probe heating
▪ A 0: Automatic, Off; A 1: Automatic, On
▪ 1: Manual, On
▪ 0: Manual, Off
Lambda probe calibration (probe must be at 21% O2)
▪ YES: After activation of the Lambda probe heating, the
Lambda probe can be calibrated.
▪ NOTICE! The Lambda probe must be at 21% oxygen
(air)!
Automatic lambda probe calibration active
▪ YES: If the boiler is in one of these statuses (“
Boiler
off
”
,
“
Off
”,
or
“
Standby
”) for a minimum period,
which can be set (“
Minimum time at
standstill
”), the broadband probe will be calibrated
to 21%.
For boilers with automatic loading, calibration is carried
out at the next start (status “
Preparation
”).
For boilers with manual loading, the boiler changes to
the “
sensor check
” status after this time has elapsed
(additional indication on the display). The ID fan is
activated and the secondary air is completely opened. If
the insulated door is opened in this status, the process
is aborted.
The prerequisite for calibration is that the probe
provides a stable measurement for one minute. If the
measurement exceeds 21% for more than one minute,
the probe is also calibrated, regardless of the standstill
times.
Minimum time at standstill
Defines the duration that the boiler must be in “
Boiler
Off
”, “
Off
” or “
Standby
” mode to start automatic Lambda
sensor calibration.
Residual oxygen above which the lambda probe is allowed
to switch off
If the boiler switches to “
Boiler off
” or “
Off
” mode, the
lambda probe heating remains active for at least 1 hour,
up to a maximum of 24 hours. If the residual oxygen
content exceeds the value set here, the lambda probe
heating is switched off.
4
Parameters overview
System
64
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Summary of Contents for Lambdatronic P 3200
Page 85: ...6 Notes Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 85...
Page 86: ...6 Notes 86 Froling GesmbH A 4710 Grieskirchen Industriestra e 12 www froeling com...
Page 87: ...Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 87...