Switching-type sensor
Setting
Lambda values
Switching-type sensor
Residual oxygen content
Display of the current residual oxygen content.
Lambda probe voltage measured
Display of the current measured Lambda probe voltage.
Lambda probes correction value
Correction value for lambda measurement. If too much is
displayed, this value must be set to positive, if too little is
displayed, the value must be set to negative.
Lambda probe voltage corrected
Display of the measured Lambda probe voltage, at which
the
“Lambda probe correction value”
is taken into
account.
Broadband probe
Setting
Lambda values
Broadband probe
Residual oxygen content
Display of the current residual oxygen content.
Broadband probe heating current
Display of the measured broadband probe heating current.
Broadband probe heating voltage
Display of the measured broadband probe heating voltage.
Broadband probe Nernst voltage
Display of the measured Nernst voltage of the broadband
probe.
Broadband probe pump current
Display of the measured broadband probe pump current.
Broadband probe internal resistance
Display of the measured internal resistance of the
broadband probe.
Set - Quantity of heat calculation
Flow temperature sensor correction value
If, at the same ambient temperature, the flow temperature
sensor and return feed sensor display different
temperature values, this correction value is used to
calibrate the difference between the flow sensor and the
return sensor to "0". The corrected value is used only to
calculate the quantity of heat does not affect the operation
of the boiler. If the boiler temperature is used to calculate
the quantity of heat, the correction value is applicable to
the boiler sensor.
Flow temperature sensor input
Sensors 1/2 on the core module or a sensor on the
hydraulic module can be used as flow temperature
sensors. If an invalid sensor assignment is made, the
value of the boiler sensor is used to calculate the quantity
of heat.
Parameters overview
4
System
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
65