5.2 Boiler operating statuses
Preparation
The boiler is ventilated, the grate is closed, the sealing slider is opened and the Lambda probe
is heated.
Heating up
The combustion chamber is filled with pellets.
Pre-heating
The ignition switches on and the pellets are preheated until a bed of embers is formed. For this
period infeed is deactivated.
Ignition
The pellets are ignited with the ignition. The flame is distributed throughout the entire
combustion chamber. Infeed is controlled according to the settings in the "Ignition" parameter
menu.
Heating
The boiler controller controls combustion according to the boiler setpoints.
Slumber
The boiler has no power consumption. ID fan and infeed are deactivated.
Cleaning
The Lambdatronic carries out the cleaning program. The grate and, if necessary, the heat
exchanger are cleaned.
Shutdown wait
When the boiler is interrupted during the heating up procedures (heating up, pre-heating,
ignition), it waits for a specified period of time until the next start attempt.
Shutdown wait 1
The ID fan runs to burn the remaining pellets. Infeed is deactivated.
Shutdown wait 2
The system is still ventilated by chimney draught. Infeed is deactivated.
Fault
CAUTION - There is a fault!
Standby
The Lambdatronic controls the connected heating components. The boiler waits for a start
request from the hydraulic system.
Boiler off
The boiler controller controls the connected heating components. All parts of the boiler are
deactivated. Chamber discharge system active!
FAQ
5
Boiler operating statuses
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
75
Summary of Contents for Lambdatronic P 3200
Page 85: ...6 Notes Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 85...
Page 86: ...6 Notes 86 Froling GesmbH A 4710 Grieskirchen Industriestra e 12 www froeling com...
Page 87: ...Notes 6 Service Manual Lambdatronic P 3200 for pellet boiler 4 3 Touch B1620121_en 87...