2.3.1 Connecting the bus cable
For the bus connections between the individual modules, cable type LIYCY paired 2x2x0.5 should be used. The
connection to the 5-pin plugs should be carried out according to the following diagram:
Braided shield
white
green
yellow
brown
Braided shield
white
green
yellow
brown
2.3.2 Setting end jumpers
NOTICE! To ensure smooth running of the bus system, the jumper must be set on the first and last module.
When using a bus repeater, the two galvanically separated sub-networks must be considered separately. The
jumpers for each network must be set on the first and last module.
End jumper not set
End jumper set
If the contacts at the base of the end jumper are not bridged (image left), it is referred to as “not set". In this
case there is no bus termination. If the contacts are closed (image right), the end jumper is set and the bus
connection is terminated.
Power connection and wiring
2
BUS connection
Service Manual Lambdatronic P 3200 for pellet boiler (4,3" Touch) | B1620121_en
25