2.5.2 System 0 (two heating circuits)
N
AUF
ZU
N
AUF
ZU
L
N
L1
N
L
N
Mischer 2
(30)
HKP 0 /
Brennerrelais
(34)
Heizkreis-
pumpe 1
(33)
Heizkreis-
pumpe 2
(32)
Mischer 1
(31)
PWM/0-10V
Pumpe 1 (26)
V
orlauf-
fühler 1 (23)
V
orlauf-
fühler 2 ( 22)
Durchfluss-
messer (12)
L
N
Netz
(29)
L
N
Pumpe 1
(28)
L
V
Fühler 1 (18)
Fühler 2 (17)
Betriebs-
signal
(35)
2
2
3
3
4
4
3
M
M
M
Fröling PECO
Flow temperature sensor 1/2
Heating circuit pump 1/2
Mot. mixing valve 1/2
HKP0
Balancing
valve
Note:
The minimum flow through rate of the Pellet boiler shall be respected!
(e.g. with zone valve)
PECO 15 = 260 l/h
PECO 30 = 520 l/h
PECO 20 = 340 l/h
PECO 32 = 550 l/h
PECO 25 = 430 l/h
PECO 35 = 600 l/h
If deviating from the default configuration, the following changes must be made:
❒ Deactivate DHW tank 01
❒ Activate heating circuit 02
⇨ See "Setting the system selection" [page 34]
If a zone valve is used for the minimum flow volume:
❒ In the service menu of the storage tank, set the “
Pump output for skimming
” parameter to “HCP 0”
2
Power connection and wiring
Connection options with standard delivery
30
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com