2.2.6 Analogue module
FRANA12
8 7 6 5 4 3 2
GND
1
8 7 6 5 4 3 2 1
AN-01
(Eingänge)
AN-02
(Ausgänge)
GND
+24V
- + S
AN-03
(Bus)
AN-04
(Bus)
AN-06
(Thermoelement)
AN-05
(Versorgung)
Analogue module
Module address
End jumper
Connection / Name
Note
AN-01
Inputs 1…8
Connection cable
1)
1 x 0.75 mm²
AN-02
Outputs 1…8
Connection cable
1)
1 x 0.75 mm²
AN-03
Bus
CAT 5 patch cable grey RJ45 SFTP 1:1 configuration
AN-04
Bus
AN-05
Power supply
24 V power supply of the module, connection cable
1)
2 x 1.0 mm²
- Firewood boiler: Supply via 24 V power supply unit
- Pellet boiler and dual fuel boiler: Pellet module, “MIN sensor” terminal
- Wood chip boiler: Supply via 24 V power supply unit
AN-06
Thermocouple
Use sensor connection
1.YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5
Standard configuration – Analogue module with address 0
Input
Designation
3
External power specification (0-10V)
2
Power connection and wiring
Expansion modules
26