Source for ext. power demand (0 - off, 1 - 0-10V, 2 -
Modbus)
Invert ext. power demand via analogue input
Input external power demand
Current external power demand
Adopt specified material values
YES: The preset boiler parameters for the chosen fuel
selection are adopted. When the process is completed the
parameter changes back to “NO”.
Adopt specified boiler values
YES: The preset boiler parameters for the selected boiler
type are adopted. When the process is completed the
parameter changes back to “NO”.
Adopt standard settings (all values are reset)
▪ YES: Adopting standard factory settings. This resets all
parameters! Once the settings have been applied, the
parameter automatically switches to “NO” and the boiler
must be reset; otherwise, boiler functioning is no longer
guaranteed.
EEPROM reset
▪ YES: All boiler settings and system configurations are
deleted. The boiler is only functional again once it has
been recommissioned by Froling customer services or
authorized installer.
Analogue module input for external power demand
Boiler - General settings - MODBUS settings
System menu
Boiler
MODBUS
settings
COM 2 is used as a MODBUS interface
▪ NO: The COM 2 interface sends the most important
boiler values every second.
▪ YES: The COM 2 interface can be used to connect a
MODBUS (RTU/ASCII)
MODBUS address
Defines the address of the boiler in the Modbus network.
MODBUS protocol (1 – RTU / 2 – ASCII)
Indicates which Modbus protocol is to be used for the
transfer. Which protocol must be used can be found in the
documentation of the Modbus system used on site.
Use MODBUS protocol 2014?
Indicates whether the Modbus protocol 2014 is to be used
for communication. In this version, parameters can be
written at the customer level. In addition to the previous
version, the element addresses are newly grouped
thematically.
If the parameter is set to “NO”, the functionality and the
element addresses remain the same as in the previous
version to ensure compatibility with existing systems in the
event of software updates.