Description
S3 Turbo 18
S3 Turbo 28
Testing institute
TÜV Austria
1)
TÜV Austria
1)
Test report no.
11-U-407/SD
2)
11-U-407/SD
2)
Date of issue
22/07/2011
22/07/2011
Boiler class as per EN 303-5:2012
5
5
Boiler efficiency
%
91.1
92.3
1.TÜV Austria Services GmbH, Geschäftsbereich Umweltschutz, Am Thalbach 15, A-4600 Thalheim/Wels
2.As per ÖNORM / DIN EN 303-5, Section 5.1.3 type test: For a boiler from a range with a consistent nominal output from the largest to the
smallest boiler ≤ 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers
fulfil the requirements of the norm, including those in a specific range that have not been tested, which have values that have been deter‐
mined depending on nominal output by interpolation.
Test data - Emissions in [mg/MJ]
1)
(nominal load)
Carbon monoxide (CO)
mg/MJ
90
58
Nitrogen oxide (NOx)
mg/MJ
91
83
Organic hydrocarbons (OGC)
mg/MJ
6
3
Dust
mg/MJ
7
7
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load)
Carbon monoxide (CO)
mg/m³
133
86
Nitrogen oxide (NOx)
mg/m³
134
123
Organic hydrocarbons (OGC)
mg/m³
10
5
Dust
mg/m³
11
10
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Description
S3 Turbo 36
S3 Turbo 45
Testing institute
TÜV Austria
1)
TÜV Austria
1)
Test report no.
11-UW/Wels-
EX-128/4
2)
11-UW/Wels-
EX-128/5
Date of issue
21/07/2011
07/11/2011
Boiler class as per EN 303-5:2012
4
5
Boiler efficiency (nominal load / partial
load)
%
93.0 / 92.5
94.1 / 92.7
1.TÜV Austria Services GmbH, Geschäftsbereich Umweltschutz, Am Thalbach 15, A-4600 Thalheim/Wels
2.The emissions values for the partial load are determined in accordance with the test drawing 10-U-665/SD of 16/12/2010 as indicated in
point 1.6 (a) and point 6 in the test report no. 11-UW/Wels-EX-128/4 of 21/07/2011.
Test data - Emissions in [mg/MJ]
1)
(nominal load/partial load)
Carbon monoxide (CO)
mg/MJ
39 / 380
55 / 190
Nitrogen oxide (NOx)
mg/MJ
79 / 76
85 / 86
Organic hydrocarbons (OGC)
mg/MJ
1 / 15
2 / 7
Dust
mg/MJ
7 / 9
9 / 10
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load)
Carbon monoxide (CO)
mg/m³
58 / 559
81 / 280
Nitrogen oxide (NOx)
mg/m³
116 / 111
125 / 127
Organic hydrocarbons (OGC)
mg/m³
2 / 23
3 / 11
Test report data
S3 Turbo 18 - 28
Test report data
S3 Turbo 36 - 45
Technology
3
Technical specifications
Installation Instructions S3 Turbo | M1080813_en
17
All manuals and user guides at all-guides.com