DO2633
The module has 2 Triac outputs (2x phase control), 2/3 line terminal. The power supply (L and N) are
fed directly to the module.
NOTICE! This module must only be used with a BM32 bus module.
LED
Colour
Status
Description
r
Green
Off
Not in operation (no power supply)
Quick flashes
Reset mode
Flashing
Preoperative mode
On
Module in operation
e
Red
Off
No error / no supply to module
On
Error or reset status
Quick flashes
Zero-crossing signal has failed (no input/output
voltage or input/output voltage too low)
e+r
Red illuminated (e)
Green flashing (r)
Incorrect firmware
1-2
Orange
Control status of corresponding digital output
Electric components and wiring
7
PLC
Service manual SPS 4000 | B0960622_en