4 Initial startup
4.1 Before switching on for the first time
NOTICE
You should have the initial startup carried out by the authorised heating engineer from Froling
customer services.
❒ Check that there are no foreign bodies in the control cabinet (pieces of wire, washers, screws etc.)
❒ Performing wiring check:
Check for loose, non-insulated wires that can cause a short circuit
❒ Check the pin assignment of pumps, mixers and other units that are NOT pre-assembled by Froling
❒ Check that there is adequate nominal current at the system's main fuse
❒ Check all motor protection switches for correctly set nominal current of the units
❒ Before switching on by the main switch for the first time, check power supply line for correct voltage
4.2 Switching on for the first time
❒ Turn on the main switch
➥ There is voltage at all of the boiler's components
➥ After the system start of the controller, the boiler type is set to the default “Turbomat TM 150” and the
SPS hardware is not configured
❒ Before setting the boiler type, perform a software update and start the hardware detection