5 Menus and parameters
5.1 Environment
5.1.1 Distributor 1... 4
Settings
System menu
Environment
Distributors
Settings
Name
Freely selectable name for the respective distributor.
Mode
Switching the distributor on and off
▪ On: All of the components assigned to the distributor
are controlled based on the set parameters.
▪ Off: Requests of the components assigned to the
distributor are ignored
Minimum speed of pump
Prerequisite: Distributor without storage tank
To adjust the minimum speed to the pump type (set mode
of pump in accordance with pump manufacturer).
Maximum speed of pump
Prerequisite: Distributor without storage tank
The speed control of the distributor pump is limited to this
value (e.g. in case of a systemic adjustment of the
maximum pump speed).
DHW priority
If this parameter is active, the heating circuits are
deactivated during active boiler loading in order to ensure
fast hot water preparation.
Enable heating circuit
Prerequisite: A storage tank and one or more heating
circuits were assigned to the distributor
Defines the temperature value in the top part of the buffer
tank from which the heating circuit pumps are released.
The value applies for all heating circuits assigned to the
distributor.
Storage tank distributor 1... 4
System menu
Environment
Distributors
Storage tank
⇨ See "Storage tank" [page 31]
Menus and parameters
5
Environment
Service manual SPS 4000 | B0960622_en
29