5.3.15 Control parameters
System menu
Boiler
Control parameters
Power calculation attenuation
Specifies the delay time in seconds, when the DDC signal
is changed from 0 to 100%.
Min. power at minimum combustion chamber temperature
and flue gas temperature
Specifies the minimum boiler power at minimum flue gas
temperature or minimum combustion chamber
temperature.
Induced draught Kp
Proportional value of the PI controller for the induced
draught.
Induced draught Tn
Reset time of the PI controller for the induced draught.
Boiler-Kp
Proportional value of the PI controller for the boiler
controller
Boiler-Tn
Reset time of the PI controller for the boiler controller