WARNING reporting chain delay
For signal chains with external systems, the forwarding of
warning messages is delayed by this value.
FC warnings delay
In order to ignore short FC error messages, the fault must
last at least this length of time to be detected
Delay error boiler doors
For signal chains with external systems, the forwarding of
alarm messages is delayed by this value.
Issuing of warnings to the linked/cascade participants
Defines whether warnings from the linked/cascade
participants should be displayed on the boiler.
Issuing of errors to the linked/cascade participants
Defines whether faults on the linked/cascade participants
should be displayed on the boiler.
Shutdown delay at a fault
If a fault occurs, at least the set time is displayed. This is
particularly sensible if external dialling devices are
connected, that only check the state periodically.
User-defined messages
System menu
Diagnosis
Message
forwarding
User-defined
messages
Message text
Defines the text of the freely assignable message shown
on the display.
Message type
Defines the type of message that affects the behaviour of
the boiler.
▪ Info: Message is displayed only once
▪ Warning: Message is displayed; the boiler continues to
run normally. If the digital input for this message
remains in use, the message is displayed again after a
certain period of time.
▪ Error: Message is displayed and the boiler is shut down
in a controlled manner.
▪ Alarm: Message is displayed and the boiler is shut
down in an uncontrolled manner (EMERGENCY
STOP).
Message delay
Defines the delay in seconds until the message is
triggered after the event occurs.
5
Menus and parameters
Diagnosis