Example 2: Rotary agitator with separate drive system on two users
Rotary agitator with
separate drive
Feed screw 2
Feed screw 1
Feed screw 3
Master
Slave 1
Feed screw 1
Feed screw 2
Parameterization procedure for this example at the master system:
❒ In the “
Feeder unit
” menu set the “
Feed screw
” parameter to “3”
❒ In the "
Chamber discharge system
" menu set the “
Rotary agitator separately driven
"
parameter to “1”
❒ In the “
Order / Configuration
” menu tap on the first entry “
Stoker
”
❒ For the “
Stoker is loaded by
” parameter select the entry “Feed screw 1”
❒ In the “
Cascade user
” submenu for parameter “
Boiler 2 loaded by
” select the entry “Rotary agitator
separately driven 1”
Menus and parameters
5
System configuration
Service manual SPS 4000 | B0960622_en
83