Module clamping position
Defines the channel of the respective card. Please refer to the technical description for the number of channels,
counting method and connection.
IO type
To set the type of evaluation/activation:
1. Digital inputs: N/C contact / N/O contact
2. Analogue inputs and outputs: 0-20 mA, 4-20 mA, 0-10 V, 2-10 V
3. Temperature inputs: PT 100, PT 1000, KTY81-210
Minimum and maximum
Scaling of the respective sensor.
Example: IO type = 4-20 mA, minimum = 0.0 mbar, maximum 400.0 mbar
An IO value at the analogue input of 4.00 mA corresponds to a scaled value of 0 mbar. If 12.00 mA are present
at the input, this would correspond to 200 mbar.
Offset:
Offset sensor calibration, setting range of ±3% from the maximum.
IO mode
Quick selection for input/output mode.
Off
The value at the input is ignored (corresponds to the value “0”) or the output is switched off independent of the
current status.
Auto
The value at the input is evaluated or the calculated value is issued at the output.
On (digital inputs and outputs)
The input/output is switched on independently of the current status.
On with value (analogue inputs and outputs)
The input/output is activated with the specified value irrespective of the current value.
General information
1. Node numbers:
When the node number is set, the socket number and the module clamping position are automatically filled
in. Conversely, the node number is also calculated automatically.
2. All settings in the change dialogue box are only applied by tapping on the apply or confirm icon.
Menus and parameters
5
System configuration
Service manual SPS 4000 | B0960622_en
87