23
EN
(6)
NO/alarm terminals
S3 - 2 EXT
for connecting an external NO contact, e.g. to isolate the device from the
grid voltage using an AC contactor;
connected using bracket when delivered.
3 - 4
IN1
for connecting and evaluating a floating alarm contact
5 -6
IN2
for connecting and evaluating a floating alarm contact
7 - 8
IN3
for connecting and evaluating a floating alarm contact
The contacts must be potential-free.
Contact rating 24 V / 10 mA
Cable cross-section: 0.5 - 6 mm²
Tightening torque of terminals: 0.8 - 1.6 Nm
(7)
'Solar Net' LED
shows the current status of the Fronius Solar Net
(8)
Fuse F1 for switched-mode power supply, 4 A slow-blow
Item
Description
| S3 EXT 2 | 3 IN1 4 | 5 IN2 6 | 7 IN3 8 |
Summary of Contents for Agilo 100.0-3
Page 2: ...0...
Page 4: ...2...
Page 8: ...6...
Page 13: ...General information...
Page 14: ......
Page 30: ...28...
Page 31: ...Installation and commissioning...
Page 32: ......
Page 51: ...49 EN 1 2 Inserting the fuse grounds the solar modules on the negative pole 1 1 1 2 2...
Page 53: ...51 EN 2 3 Tightening torque 3 Nm 1 3 2 4 5 4 3 2 4 5 1 5...
Page 57: ...Operation...
Page 58: ......
Page 84: ...82...
Page 85: ...Troubleshooting and maintenance...
Page 86: ......
Page 107: ...Appendix...
Page 108: ......