24
Possible relay
contact functions
(9)
Relay output terminals
NC1
NC for relay contact 1
SC1
Relay contact 1
NO1
NO for relay contact 1
NC2
NC for relay contact 2
SC2
Relay contact 2
NO2
NO for relay contact 2
Cable cross-section: 0.5 - 6 mm²
Tightening torque of terminals: 0.8 - 1.6 Nm
Max. continuous current: 16 A
Switching load: 500 mW (10 V / 5 mA)
Switching capacity: 16 A / 250 V (AC1) and 16 A / 30 V (DC1)
The relay outputs are not protected.
Relay contacts can be assigned different functions in the Basic service menu. The
access code 22742 must be entered to access the Basic service menu:
-
Press the 'Menu' key
-
Select 'Setup' mode
-
Press the unassigned 'Esc' button five times
-
Enter the access code 22742
-
Select the 'Switch contact 1' or 'Switch contact 2' parameter
-
Set the desired relay contact function
(10)
F2 fuse, 4 A slow-blow
Item
Description
| NC1 SC1 NO1 | NC2 SC2 NO2 |
Function
Switch contact ac-
tivation criterion
1)
Switch contact de-
activation criteri-
on
2)
Description
Off
-
Permanently OFF
Function switched
off
On
Permanently ON
-
Test function for NO/
alarm contact
AC Open
AC contactor is open
AC contactor is
closed
No contactor error
signal or AC grid
Summary of Contents for Agilo 100.0-3
Page 2: ...0...
Page 4: ...2...
Page 8: ...6...
Page 13: ...General information...
Page 14: ......
Page 30: ...28...
Page 31: ...Installation and commissioning...
Page 32: ......
Page 51: ...49 EN 1 2 Inserting the fuse grounds the solar modules on the negative pole 1 1 1 2 2...
Page 53: ...51 EN 2 3 Tightening torque 3 Nm 1 3 2 4 5 4 3 2 4 5 1 5...
Page 57: ...Operation...
Page 58: ......
Page 84: ...82...
Page 85: ...Troubleshooting and maintenance...
Page 86: ......
Page 107: ...Appendix...
Page 108: ......