37
EN
Safety
Connecting the
inverter to the
public grid
IMPORTANT!
Minimum cable cross section for the ground conductor PE:
10 mm² für Copper wire
16 mm² für Aluminium wire
1
WARNING!
An electric shock can be fatal. Danger due to grid voltage and DC
voltage from solar modules that are exposed to light.
-
Make sure that both the AC side and the DC side of the inverter are de-ener-
gised before carrying out any connection work.
-
Only an authorised electrical engineer is permitted to connect this equipment
to the public grid.
CAUTION!
Risk of damage to the inverter as the result of incorrectly tightened ca-
ble connections. Incorrectly tightened cable connections can cause heat damage
to the inverter that may result in a fire. When connecting AC and DC cables, en-
sure that all the cables are tightened to the inverter terminals with the specified
torque.
CAUTION!
Risk of damage to the inverter due to the ingress of moisture.
-
Never open the inverter during rain.
-
Do not establish any connections or carry out any maintenance work during
rain.
NOTE!
Ensure that the phases are connected in the right order: L1, L2, L3, N and
PE.
After connecting the phases, check the rotary field of the grid using a rotary field
measuring device. The inverter is designed for a clockwise rotary field.
1
AC
OFF
1
Summary of Contents for Agilo 100.0-3
Page 2: ...0...
Page 4: ...2...
Page 8: ...6...
Page 13: ...General information...
Page 14: ......
Page 30: ...28...
Page 31: ...Installation and commissioning...
Page 32: ......
Page 51: ...49 EN 1 2 Inserting the fuse grounds the solar modules on the negative pole 1 1 1 2 2...
Page 53: ...51 EN 2 3 Tightening torque 3 Nm 1 3 2 4 5 4 3 2 4 5 1 5...
Page 57: ...Operation...
Page 58: ......
Page 84: ...82...
Page 85: ...Troubleshooting and maintenance...
Page 86: ......
Page 107: ...Appendix...
Page 108: ......