47
EN
Grounding the solar modules in the inverter
General
Some manufacturers of solar modules stipulate that the module must be grounded.
Locking ring for solar module grounding on the negati-
ve pole
Inside the inverter is a means for grounding
solar modules to the negative pole via a fu-
se.
Grounding the
solar module to
the negative pole
via a fuse
Fronius recommends the following fuse when grounding the solar module to the negative
pole:
nominal current rating 3 A / 1000 V, fuse dimensions 10 x 38 mm
IMPORTANT!
Fuses for grounding the solar module are not part of the scope of supply of
the inverter. If the manufacturer of the solar module stipulates that grounding is required,
an appropriate fuse must be ordered separately
Grounding the solar module to the nega-
tive pole via a fuse
(1)
Solar module
(2)
Inverter
(3)
Fuse
WARNING!
An electric shock can be fatal. Danger of electric shock if the solar
module is not grounded or is not grounded properly.
To comply with IEC 62109-2, any grounding required by the manufacturer of the
solar module within the inverter must only be carried out via the specified fuse.
DC+
DC-
N
PE
(1)
(2)
=
~
=
~
(3)
L1
L2
L3
Summary of Contents for Agilo 100.0-3
Page 2: ...0...
Page 4: ...2...
Page 8: ...6...
Page 13: ...General information...
Page 14: ......
Page 30: ...28...
Page 31: ...Installation and commissioning...
Page 32: ......
Page 51: ...49 EN 1 2 Inserting the fuse grounds the solar modules on the negative pole 1 1 1 2 2...
Page 53: ...51 EN 2 3 Tightening torque 3 Nm 1 3 2 4 5 4 3 2 4 5 1 5...
Page 57: ...Operation...
Page 58: ......
Page 84: ...82...
Page 85: ...Troubleshooting and maintenance...
Page 86: ......
Page 107: ...Appendix...
Page 108: ......