Safety inspection
Safety Inspection
This chapter describes the safety inspection for the inverter described in this service man-
ual. This chapter was produced in accordance with "DIN VDE 0701-0702" and "ÖVE/
ÖNORM E8701-1".
Please also observe the requirements and standards for your particular country, since
there may be deviations in the measured values or inspection steps.
If there are no requirements and standards for your particular country, Fronius recom-
mends that this inspection is still carried out.
The safety inspection must only be conducted on a completely assembled device.
Responsibility
The repairs technician is responsible for the proper performance and documentation of the
safety inspection, and for the correct inspection result. Fronius accepts no liability.
If a defect is identified during the inspection, the safety inspection must be repeated once
the defect has been eliminated.
The following inspection steps must be carried out in the sequence specified. Every in-
spection must be passed before the next inspection can begin. If one of the inspections
cannot be carried out, the inspector must take the decision, and the responsibility and lia-
bility falls to him regarding whether the safety of the device can still be confirmed. This de-
cision must be justified accordingly and included in the inspection log under Notes.
Scope of Applica-
tion
In principle, a "safety inspection" must be carried out after a repair/overhaul, change or ac-
cording to standard requirements from the respective country.
Qualification of
the Inspection
Personnel
The safety inspection may only be carried out by a qualified electrician. These are the peo-
ple who, on the basis of their technical training, knowledge, and experience as well as
knowledge of the applicable regulations, can assess the assigned tasks and detect and
prevent electrical and other possible dangers.
Measuring Instru-
ments
The following requirements for measuring instruments must be met as per DIN VDE 0701-
0702 and ÖVE/ÖNORM E8701-1. Individual national requirements and standards must
also be observed.
Ground conductor resistance
-
The measurement voltage may be an AC or a DC voltage.
-
The open circuit voltage may not exceed 24 V or fall below 4 V.
-
The measurement current within the measuring range between 0.2
and 1.99
may
not fall below 0.2 A.
Insulation Resistance
-
The value of the measured voltage from the measuring instrument must correspond
to at least the rated voltage of the device to be tested against grounding, but no less
than 500 V DC voltage
-
The measurement current must be at least 1 mA (this corresponds to a load resis-
tance of 0.5 M
).
Summary of Contents for Eco 15.0-3-208 US
Page 2: ...2...
Page 4: ...4...
Page 5: ...Allgemeine Informationen...
Page 6: ......
Page 8: ...8 Mess und Pr f mittel Digitales Multimeter Equipment f r die sicherheitstechnische berpr fung...
Page 9: ...Einbau State 112 KIT...
Page 10: ......
Page 15: ...15 DE 1 2 3 4 5 1 2 3 4 22 1 lbf in 2 5 Nm 5...
Page 19: ...Sicherheitstechnische berpr fung...
Page 20: ......
Page 32: ...32...
Page 34: ...34...
Page 35: ...General Information...
Page 36: ......
Page 38: ...38 Measuring and In spection Equip ment Digital multimeter Equipment for safety inspection...
Page 39: ...Installation State 112 KIT...
Page 40: ......
Page 45: ...45 EN US 1 2 3 4 5 1 2 3 4 22 1 lbf in 2 5 Nm 5...
Page 49: ...Safety inspection...
Page 50: ......
Page 62: ...62...
Page 63: ...63 EN US...