77
EN
Technical data
Fronius Agilo
360.0-3 TL
Input data
Output data
General data
MPP voltage range
505 - 820 V DC
Max. input voltage
(at 1,000 W/m²/ -10°C in an open circuit)
1000 V DC
Max. input current
730 A
Max. short circuit current of the solar modules
1095 A
Nominal output power (P
nom
)
360 kVA
Max. output power
(up to 35 °C ambient temperature)
360 kVA
Nominal grid voltage
3 ~ 330 V
Grid voltage tolerance
+15 / -20 %
1)
Nominal output current (three-phase)
629,8 A
Nominal frequency
50 / 60 Hz
1)
Total harmonic distortion
< 3 %
Power factor cos phi
0,8 - 1 ind./cap.
2)
Max. permitted grid impedance Z
max
at PCC
3)
47 mOhm
Max. feedback current
4)
-
5)
Starting current pulse
6)
-
5)
Max. output fault current per period
-
Maximum efficiency
98,50 %
Europ. efficiency
98,30 %
Overnight self-consumption
168 W
Cooling
Controlled forced-air ventila-
tion
Degree of protection
Indoor device
Outdoor device
electronic area
IP 40
IP 44
IP 55
Dimensions l x w x h
Indoor device
Outdoor device
1150 x 775 x 1970 mm
1150 x 1055 x 2230 mm
Weight
Indoor device
Outdoor device
615 kg
660 kg
Permitted ambient temperature
(at 95% rel. humidity)
- 20 °C - +50 °C
EMC device class
A
Overvoltage category AC / DC
3 / 2
Pollution level
3