Protocol type
Specifies the communications protocol to be used to transfer the data:
Device Info
For displaying the settings that will be of relevance to an energy supply company. The val-
ues shown will depend on the country setup or the device-specific settings of the inverter.
Unit
-
Setting range
Solar Net / Interface
Factory setting
Solar Net
Display area
General / MPP Tracker / Grid Monitoring / Voltage Limits / Fre-
quency Limits / P AC Reduction
General:
Setup
Country setup
Version
Version of country setup
Group
Group for updating the inverter software
MPP Tracker:
DC Mode
DC mode
FIX
Voltage value in V for fixed voltage operation
User
Voltage value in V for MPP User operation
Grid Monitoring:
GMTi
Start-up time of inverter in s
GMTr
Reconnection time in s following a grid fault
ULL
Mean grid voltage over 10 minutes in V.
LL Trip
Trip time for long-term voltage monitoring
Voltage Limits:
UIL max
Upper inner grid voltage in V
UIL min
Lower inner grid voltage in V
UOL max
Upper outer grid voltage limit value in V
UOL min
Lower outer grid voltage limit value in V