The status display of the power stage
sets "STATE PS" appears
-
Press the "Enter" key
Class 1 Status
Codes
Class 1 status codes are typically tempo-
rary. Their cause lies in the public grid.
The initial response of the inverter is to disconnect itself from the grid. The grid is subse-
quently checked for the stipulated monitoring period. If after the end of this period no fur-
ther defect is identified, your inverter resumes operating and feeding power into the grid.
101
Grid voltage not within admissible range
Behavior
Grid voltage is thoroughly tested and as soon as it is again with-
in the permissible range, the inverter will resume feeding power
into the grid.
Remedy
Check grid connections and fuses
Should the status code persist, you should contact your system
installer
104
Grid frequency not within admissible range
Behavior
Grid frequency is thoroughly tested and as soon as it is again
within the permissible range, the inverter will resume feeding
power into the grid.
Remedy
Check grid connections, breakers and disconnect
Should the status code persist, you should contact your system
installer
107
No AC grid detected
Behavior
Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy
Check grid connections and fuses
Should the status code persist, you should contact your system
installer
Summary of Contents for IG 2000
Page 2: ...0...
Page 4: ...2...
Page 6: ...4...
Page 10: ...8...
Page 15: ...General Information...
Page 16: ......
Page 21: ...Installation and Startup...
Page 22: ......
Page 50: ...48...
Page 51: ...Operation...
Page 52: ......
Page 80: ...78...
Page 81: ...Troubleshooting and Maintenance...
Page 82: ......
Page 95: ...Appendix...
Page 96: ......
Page 113: ...111 EN US...
Page 114: ...112...
Page 115: ...113 EN US...