103
EN
751
Real-time clock lost
1. Inverter has not been able to
establish an AC connection for
more than 5 days
1. Setting the time
2. Faulty Recerbo memory
2. Replace Recerbo
754* - 755*
Time set
1. Date/time has been set
757
Time cannot be saved; for
safety reasons the inverter
is not feeding in power
1. Faulty real-time clock
1. Replace Recerbo
758
RTC quartz does not work
in emergency mode
1. Occurs once
1. Automatic correction
2. Faulty Recerbo
2. Faulty Recerbo
760
Faulty system quartz
1. Occurs once
1. Automatic correction
2. Faulty Recerbo
2. Replace Recerbo
761*
Read error on on-board
memory chip
1. On-board memory chip
missing
1. Replace interface PC board
with on-board memory chip
2. Faulty ribbon cable
2. Replace ribbon cable
3. Faulty Recerbo
3. Replace Recerbo
4. Faulty on-board memory
chip
4. Replace inverter
762*
Read error on on-board
memory chip
1. Integrated memory chip
missing
1. Use/install original memory
chip
2. Faulty ribbon cable
2. Replace ribbon cable
3. Faulty Recerbo
3. Replace Recerbo
4. Faulty integrated memory
chip
4. Replace inverter
763*
Power limitation on on-
board memory chip cannot
be read
1. On-board memory chip
missing
1. Use/install original memory
chip
2. Faulty Recerbo
2. Replace Recerbo
3. Faulty on-board memory
chip
3. Replace inverter
765*
Recerbo cannot read power
limitation
1. Faulty Recerbo
1. Replace Recerbo
766
No power limitation found
1. Faulty Recerbo
1. Replace Recerbo
2. Faulty on-board memory
chip or integrated memory chip
2. Replace inverter
767*
Power limitation cannot be
read
1. Occurs once
1. Automatic correction
2. Faulty Recerbo
2. Replace Recerbo
768
Power limitation changed
while feeding energy into
the grid
1. Integrated memory chip is
connected or switched off
while feeding energy into the
grid
1. Automatic correction (state
code must be confirmed)
772
Memory on memory chip is
not available; for safety rea-
sons the inverter is not
feeding in power
1. SSP is not connected
1. Check SSP
773
Memory on memory chip is
not initialised; for safety
reasons the inverter is not
feeding in power
1. Memory not programmed or
memory lost
1. Reload setup
2. Faulty Recerbo
2. Replace Recerbo
Code
Description
Behaviour
Remedy
Summary of Contents for Primo 3.0-1
Page 2: ...2 ...
Page 5: ...Allgemeine Informationen ...
Page 6: ......
Page 13: ...Fehler Suchhilfe ...
Page 14: ......
Page 32: ...32 ...
Page 33: ...Komponenten austauschen ...
Page 34: ......
Page 54: ...54 DC Trenner auf ON stellen 6 ...
Page 65: ...Sicherheitstechnische Überprüfung ...
Page 66: ......
Page 78: ...78 ...
Page 81: ...General information ...
Page 82: ......
Page 89: ...Error location aid ...
Page 90: ......
Page 108: ...108 ...
Page 109: ...Changing components ...
Page 110: ......
Page 130: ...130 Set the DC disconnector to ON 6 ...
Page 141: ...Safety Inspections ...
Page 142: ......
Page 154: ...154 ...
Page 155: ...Appendix ...
Page 158: ...158 ...
Page 159: ...159 ...