143
EN
Safety Inspections
Safety inspection
This section outlines the safety inspection for the device described in this service manual.
It has been structured in compliance with "DIN VDE 0701-0702” and "ÖVE/ÖNORM
E8701-1”.
Please also be aware of the requirements and standards relevant to your country, as the
measured values or steps taken during the tests may vary.
Should there be no relevant requirements and standards in your country, Fronius recom-
mends that this test should still be carried out.
The safety inspection must only be carried out on a fully assembled device.
Responsibility
The repair engineer is responsible for carrying out and documenting the safety inspection
properly and for making the correct decision regarding the outcome of the inspection. Fro-
nius accepts no liability in this respect.
Should any defects be identified during the test, then the entire safety inspection must be
repeated once such defects have been rectified.
The following tests must be performed in the prescribed sequence. Each test must be
passed before the next test is started. If it is not possible to perform a particular test, the
examiner must decide whether the safety of the device can nevertheless still be verified.
The examiner bears full responsibility and liability for this decision. Justifications for the re-
sulting decision must be documented in the test record under "Comments".
Area of applica-
tion
A safety inspection must be performed after any repair, maintenance or modification work,
or if stipulated by applicable national standards.
Inspection staff
qualifications
The safety inspection may only be performed by an appropriately qualified electrician.
These are persons who due to their specialist training, knowledge and experience of the
relevant regulations are able to evaluate the tasks they are assigned as well as to identify
and avoid electrical and other possible hazards.
Measuring instru-
ments
The following requirements concerning measuring equipment as defined by DIN VDE
0701-0702 and ÖVE/ÖNORM E8701-1 must be observed. Also refer to the applicable re-
quirements and standards in your country:
Ground conductor resistance
-
The measuring voltage may be a direct or alternating voltage
-
The open circuit voltage must remain within a range of 4 V to 24 V
-
The measuring current within the measuring range of 0.2
to 1.99
must not drop
below 0.2 A
Summary of Contents for Primo 3.0-1
Page 2: ...2 ...
Page 5: ...Allgemeine Informationen ...
Page 6: ......
Page 13: ...Fehler Suchhilfe ...
Page 14: ......
Page 32: ...32 ...
Page 33: ...Komponenten austauschen ...
Page 34: ......
Page 54: ...54 DC Trenner auf ON stellen 6 ...
Page 65: ...Sicherheitstechnische Überprüfung ...
Page 66: ......
Page 78: ...78 ...
Page 81: ...General information ...
Page 82: ......
Page 89: ...Error location aid ...
Page 90: ......
Page 108: ...108 ...
Page 109: ...Changing components ...
Page 110: ......
Page 130: ...130 Set the DC disconnector to ON 6 ...
Page 141: ...Safety Inspections ...
Page 142: ......
Page 154: ...154 ...
Page 155: ...Appendix ...
Page 158: ...158 ...
Page 159: ...159 ...